Electrical Installation (cont.)
Interfacing with basic timers, thermostats, and other equipment
When a contact closure is seen across Digital Input #4 (MI4) and DC Common (DCM), the fan is pre-programmed to issue a base-block
code and initiate fan shutdown. This is essentially turning off the fan controller’s output terminals, while leaving the fan controller in Run
mode.
Auxiliary contacts can be associated with basic timers and thermostats, as well as equipment such as overhead cranes, in order to
initiate fan shutdown simultaneously with equipment shutdown when contact closure is seen.
After the auxiliary contact has reopened, the fan will return to its previous operating mode.
MI1
MI2
MI3
MI4
MI5
MI6
DCM
DCM
24V
ACM
AVI
ACI
10V
MCM
AFM
M01
RA
RB
RC
RUN
STOP
FWD
REV
REM
LOC
U
H
F
MODE
PROG
DATA
FWD
REV
RUN
STOP
RESET
LOCAL
REM
Thermostat, timer,
or other equipment
auxiliary contact
I/O mode selection
DIP switches
RS-485
1:Reserved
2:EV
3:GND
4:SG-
5:SG+
6:Reserved
7:Reserved
8:Reserved
Digital Input
Digital Input
Digital Input
Digital Input
Digital Input
Digital Input
+24 VDC / 20 mA
ANL Common
ANL In 0-10 VDC / 47 kΩ
ANL In 4-20 mA / 250 Ω
+10 VDC / 3 mA
ANL Out; 0-10 VDC / 2 mA / 20 kΩ
Opto-Out Common
Opto-Out; Max 48 VDC / 50 mA
Digital Common