Basic Distributed I/O Interface; LOCAL Control
Note: RA to Digital Input #1 jumper removed.
The Powerfoil
®
X2.0 fan is programmed to be controlled via the included wall controller, which starts, stops, and performs speed
control duties for the fan. Fault messages and toggling between output frequency and fan RPM displays are also controlled by the wall
controller. This mode of operation is commonly referred to as “local control.”
*For the wall control unit to be active, the LOC indicator light must be illuminated by pressing the LOCAL/REM button.
Electrical Installation (cont.)
MI1
MI2
MI3
MI4
MI5
MI6
DCM
DCM
24V
ACM
AVI
ACI
10V
MCM
AFM
M01
RA
RB
RC
RUN
STOP
FWD
REV
REM
LOC
U
H
F
MODE
PROG
DATA
FWD
REV
RUN
STOP
RESET
LOCAL
REM
RS-485
1:Reserved
2:EV
3:GND
4:SG-
5:SG+
6:Reserved
7:Reserved
8:Reserved
Digital Input
Digital Input
Digital Input
Digital Input
Digital Input
Digital Input
+24 VDC / 20 mA
ANL Common
ANL In 0-10 VDC / 47 kΩ
ANL In 4-20 mA / 250 Ω
+10 VDC / 3 mA
ANL Out; 0-10 VDC / 2 mA / 20 kΩ
Opto-Out Common
Opto-Out; Max 48 VDC / 50 mA
Digital Common
FWD / STOP
REV / STOP
Required 0-10VDC
Analog Speed Reference
Optional 0-10VDC
Analog Speed
Feedback
Optional Drive Fault
Status Output
48V @ 50mA Max.
LOCAL / REMOTE
TOGGLE
“REM” indicator is Lit