background image

INSTALLATION MANUAL

ENGLISH

OFF  This disables transmitter storage via radio.
 

The transmitters can only be memorised using the appropriate Radio 
menu.

-     Loop  (

loop

) [ OFF ] 

(Advanced logics - address 11)

ON  In the case of a closed loop centralised connection (Fig.20), set the 

control unit to ON.

OFF  In the case of an open centralised connection (Fig.20), set the control 

unit to OFF.

-     Master/Slave  (

Master

) [ OFF ] 

(Advanced logics - address 12)

ON  The control panel is set as Master in a centralised connection. 
OFF  The control panel is set as Slave in a centralised connection.

15.3) RADIO MENU (

RADIO

)

-  

Add 

 

Allows you to add one key of a radio control device to the receiver 
memory;  after  storage  it  displays  a  message  showing  the  receiver 
number in the memory location (from 01 to 64).

-  

Add Start button

 

(

add start

)

 

associates the required key to Start command

 

For transmitters with hidden key, press hidden key P1 (fig. B1). 

 

For transmitters without hidden key, the key P1 function corresponds 
to  simultaneously  pressing  the  4  transmitter  keys  or,  after  opening 
the battery compartment, bridging the two P1 points by means of a 
screwdriver (fig. B2). 

-  

Read (

read

)

 

Checks one key of a receiver; if stored it displays a message showing 
the receiver number in the memory location (from 01 to 64), and the 
key number (T1, T2, T3 or T4).

-  

Eliminate list (

erease 64

)

 

WARNING!

 Completely removes all memorised radio control devices 

from the receiver memory. 

Receiver code reading

 (

RX code

)

 

This displays the code entered in the receiver.

IMPORTANT NOTE: STICK THE ADHESIVE KEY LABEL ON THE FIRST 
MEMORISED TRANSMITTER (MASTER). 

In the case of manual programming, the first transmitter assigns the RECEI-
VER KEY CODE; this code is necessary in order to carry out subsequent 
cloning of radio transmitters. 

The  on-board  Clonix  incorporated  receiver  is  provided  with  a  number  of 
advanced functions: 
•  Cloning of master transmitter (rolling-code or fixed code)
•  Cloning by replacement of transmitters already inserted in the receiver
•  Management of transmitter database 
•  Management of common receivers
To use these advanced function, refer to the 

universal palmtop programmer

 

instructions and the CLONIX programming guide, supplied with the 

universal 

palmtop programmer

 device.

15.4) LANGUAGE MENU (

language

)

Allows you to set the language on the display programmer.

-   ITALIAN (

ITA

-   FRENCH (

FRA

-   ENGLISH (

ENG

-   SPANISH (

ESP

15.5) DEFAULT MENU (

default

)

Restores the preset default values on the control unit. After restoring, a new 
autoset operation must be carried out. 

  

15.6) DIAGNOSTICS AND MONITORING

The display on the 

QSC-D UL

 panel shows some useful information, both 

during normal operation and in the case of malfunctions.

Diagnostics:

In the case of malfunctions, the display shows a message indicating which 
device needs to be checked:
PED  =  Pedestrian input activation
STRT  =  START  input activation
STOP =  STOP input activation
PHOT =  PHOT input activation

BAR  =  COST input activation 

FLT  =  FAULT input activation for checked photocells
CLOS =  CLOSE input activation
OPEN =  OPEN input activation
SWO  =  Opening limit switch input activation
SWC  =  Closing limit switch input activation

TH 

=  Activation of software thermal protection

In the case where an obstacle is found, the 

QSC-D UL

 panel stops the door 

and activates a reverse manoeuvre; at the same time the display shows the 

“AMP” message.

Monitoring

:

During the opening and closing phases, the display shows four digits sepa-

rated by a dot, for example 

35.40.

 The digits are constantly updated during 

the manoeuvre, and represent the maximum torque reached by motor 1 (

35

and the selected torque (

40

).

These values allow the torque setting to be corrected.

If the maximum torque value reached during the manoeuvre gets sensibly 

close to the value set in the parameter menu, malfunctions may occur in the 

future following wear or slight door deformation.

It is therefore advisable to check the maximum torque reached during some 

of the manoeuvres carried out in the course of installation, and if necessary 

set a value about 15-20 percent points higher in the parameter menu.

15.7) AUTOSET MENU (

autoset

)

Allows you to automatically set the Motor torque. 

WARNING! 

The autosetting operation is carried out from closing end-of-

stroke  devices.    If  Autoset  is  commanded  in  a  different  position  an  error 

message indicating “

nsvc

” will be displayed and the required manoeuvre 

will not take place.

WARNING!! 

The autoset operation is only to be carried out after checking the 

exact leaf (opening/closing) movement, and correct limit-switch activation.

Set the adequate slow-down speed: by pressing OK the message “.... .... ....” 

is displayed and the control unit commands an opening manoeuvre without 

slow-down, followed by a closing manoeuvre without slow-down during which 

the duration of the stroke is memorised. Then, the control unit commands a 

second opening manoeuvre with slow-down followed by a second closing 

manoeuvre with slow-down during which the minimum torque value neces-

sary for the movement of the leaf is automatically set. Then the control unit 

sets a slow-down speed of 8 sec. If the stroke lasts less than 8 seconds, the 
control unit sets a slow-down time equal to half stroke.
During this phase, it is important to avoid obscuring the photocells, as well as 
using the STRT, STOP, PED, CLOS or OPEN commands and the display. 
After this, if autosetting has been successfully completed, the control unit displays 
the “OK” message and, after pressing any key, returns to the Autoset menu.  
If, on the other hand, the control unit displays the “KO” message, it means 
that the autoset procedure has not been successfully completed; it is thus 
necessary to check the wear condition of the gate and the regular movement 
of the leaves before proceeding to a new autoset operation.               

WARNING!

  During  the  autoset  phase,  the  obstacle  detection  function  is 

not  active,  therefore  the  installer  must  control  the  automation  movement 
and prevent persons and things from approaching or standing within the 
automation working range. 
In the case where buffer batteries are used, autosetting must be carried out 
with the control panel supplied by mains power voltage.

WARNING: the torque values determined by autosetting refer to 

the slow-down speed determined by autosetting. When modifying 

the slow-down speed, the slow-down torque values must be modified 

as well so that activation of the safety device takes place according 

to the new speed set.

Incorrect  sensitivity  setting  can  cause  injuries  to  persons  or  
animals, or damage to things.

16)  SERIAL CONNECTION USING SCS1 BOARD (Fig.20).

The 

QSC-D UL 

control panel allows several automation units to be connected 

in a centralised way by means of appropriate serial inputs and outputs (SCS1). 
This makes it possible to use one single command to open and close all the 
automation units connected.

Following the diagram in Fig. 20,  proceed to connecting all the  

QSC-D UL

 

control panels, exclusively using a telephone-type line. 

Should a telephone cable with more than one pair be needed, it is indispen-

sable to use wires from the same pair.

The length of the telephone cable between one appliance and the next 

must not exceed 820,2ft (250 m).

At this point, each of the QSC-D control panels must be appropriately con-

figured, by setting a MASTER unit first of all, which will have control over all 

the others, to be necessarily set as SLAVE (see logic menu).

Also set the Zone number (see parameter menu) between 0 and 127. 

The  zone  number  allows  you  to  create  groups  of  automation  units, 

each one answering to the Zone Master unit.

 Each zone can only be 

assigned one Master unit, the Master unit in zone 0 also controls the Slave 

units in the other zones.

Loop closing of the serial connection (indicated by a dotted line in Fig.20) 

is only needed if you require to check the no. of the connected devices by 
means of 

universal palmtop programmer

.

16.1) Opposite sliding leaves (Fig. 20A)

Serial connection also provides centralized control of two opposite sliding 

gates (Fig. 20A).

16 -

 DEIMOS  BT UL Ver. 07

D811419_07

Summary of Contents for DEIMOS BT KIT UL

Page 1: ...Tel int 39 0445 696533 Fax 0445 696522 Internet www bft it E mail sales bft it ATTUATORE IN BASSA TENSIONE PER CANCELLI SCORREVOLI A CREMAGLIERA LOW VOLTAGE ACTUATOR FOR RACK SLIDING GATES DEIMOS BT U...

Page 2: ...ll automazione avvalersidipersonalequalificato installatore Annualmente far controllare l automazione da personale qualificato L entrata riservata ai veicoli Prevedere un entrata separata per i pedoni...

Page 3: ...y branches or shrubs Foranydirectassistancetotheautomationsystem requesttheassistance of a qualified technician installer Have qualified personnel check the automation system once a year Entrance is r...

Page 4: ...ono disponibili i seguenti accessori opzionali Kit batteria tampone mod SBBAT Incorporabile nell attuatore consente il funzionamento dell automazione anche se manca per un breve periodo l alimentazion...

Page 5: ...del l uso del cancello e non risolve problemi dovuti a difetti e deficienze di installazione o di mancata manutenzione del cancello stesso Togliere il prodotto dall imballo e verificarne l integrit S...

Page 6: ...ci CEI 64 8 IEC364 armonizzazione HD384 ed altre norme nazionali ATTENZIONE Per il collegamento alla rete utilizzare cavo multipolare di sezione minima 3x16AWG e del tipo previsto dalle normative vige...

Page 7: ...i rallentamento in chiusura e in apertura si ottiene cro nometrando la durata di una manovra ed impostando un valore minore in questo parametro Se ad esempio la durata di una manovra di 15 secondi imp...

Page 8: ...UTOset Consente di effettuare il settaggio automatico della Coppia motori ATTENZIONE L operazione di autosettaggio va effettuata da finecorsa di chiusura Se si prova ad effettuare l Autoset in una pos...

Page 9: ...la manopola non viene riportata nella posizione iniziale azionamento motorizzato Per ripristinare il comando motorizzato ruotare la manopola in senso antiorario per tutta la sua corsa e togliere la ch...

Page 10: ...M P OK OK PM P B M ON OFF ML P OK OK AMB 11M ON OFF M P OK OK OK P R T LMPK OK OK P R T LMPK AF OK OK P T P OK OK 8MLC P OK OK P A P OK OK P A AF P OK 1R P ON OFF M P OK OK MM ON OFF M P OK Fig A OK P...

Page 11: ...M L QAMQRM PGJ QAG R QRM BCQGBCP RM 0 CEEG MENU RADIO AGGIUNGI Consente di aggiungere un tasto di un radiocomando nella memoria della ricevente dopo la memorizzazione restituisce numero del trasmettit...

Page 12: ...he drive relays and safety devices photocells and safety edge before carrying out any manoeuvre M Motor R Reduction gear with worm screw and wheel F Electromechanical limit switch unit P Pinion S Rele...

Page 13: ...laced in order to fix the reduction gear unit fig 3 If the sliding track is already there digging must be partly carried out in the track foundation casting This way should the track foundation castin...

Page 14: ...able having a minimum cross section of 3x16 AWG and complying with the current standards For example if the cable is not protected it must be at least equal to H07 RN F whereas if it is protected it m...

Page 15: ...otor torque between 1 and 99 Slow down closing motor torque cls t slow 50 Advanced parameters address 9 Set the numerical value of the motor torque between 1 and 99 Fast Opening Time op speed time 15...

Page 16: ...rque reached during some of the manoeuvres carried out in the course of installation and if necessary set a value about 15 20 percent points higher in the parameter menu 15 7 AUTOSET MENU autoset Allo...

Page 17: ...erned In the case where a release knob with personalised key is fitted fig 18 proceed as follows Insert the personalised key in the lock and rotate the key anti clockwise Grip the release knob and rot...

Page 18: ...1 max 99 Fast opening time value expressed in seconds default 15 15s min 1 1s max 2 2 min Fast closing time value expressed in seconds default 15 15s min 1 1s max 2 2 min Slow down numerical value de...

Page 19: ...adio control device QR PR FGBBCL SRRML PCJC QC BCQGPCB SRRML 0 0 OK OK OK 0 1 R 06 OK OK OK OK RADIO MENU ADD Allows you to add one key of a radio control device to the receiver memory after storage i...

Page 20: ...8 249 mm 5 1 131mm 4 6 118 mm 6 2 160mm 10 4 265 mm 4 8 122 mm 1 9 50 mm 0 8 2 2 m m 1 7 4 3 m m Min 3 9 100mm Z14 Z 1 4 p 2 2 5 6 m m 0 9 25mm Min 2 9 75mm AXI PIGNON RITZELACHSE CENTRO PINON CENTRO...

Page 21: ...m 1 2 32mm 1 1 28mm 0 8 22mm 0 8 22mm DX SX Min 1 9 50mm NO OK push the control button or use the emergency relase In the event a person is trapped under the door Always keep a closing door within sig...

Page 22: ...2 S 24V 25W Max M 19 20 NO NO FAULT COM PED 21 22 23 24 25 26 COM 5 NC SWC NC SWO 24V JP2 JP3 JP1 0V 1 2 3 4 6 7 9 10 12 13 11 8 14 15 16 17 18 ANT Grigio Grey Gris Grau Gris Cinzento Grigio Grey Gris...

Page 23: ...te Contactos Contatos Contatti Contacts Contacts Kontakte Contactos Contatos 1 3 4 1 2 2 3 4 P1 P1 T1 Led T2 P1 P1 T1 T2 T3 T4 P1 P1 T1 Led T2 P1 P1 T1 T2 T3 T4 P1 P1 UNIFLAT UNIFLAT UNIMITTO UNITRC U...

Page 24: ...24 21 35 36 13 12 13 12 13 12 13 12 13 12 13 12 13 12 24 21 35 36 38 39 37 21 18 40 21 18 37 Rx 2 Rx 1 Tx 2 Tx 1 1 2 3 4 5 1 2 1 2 1 2 3 4 Rx 4 Rx 3 Tx 4 Tx 3 1 2 3 4 5 5 5 1 2 1 2 1 2 3 4 Rx 3 Tx 3...

Page 25: ...SCS1 SCS1 Max 250m TX1 TX2 RX1 RX2 TX1 TX2 RX1 RX2 TX1 TX2 RX1 RX2 SCS1 QSC D UL Fig 20A TX1 TX2 RX1 RX2 35 36 37 38 35 36 37 38 STOP SWO1 CC1 21 22 23 24 7 25 26 NC PHOT NC NC SWC1 6 NC SWO2 CC2 21 2...

Page 26: ...26 DEIMOS BT UL Ver 07 D811419_07...

Page 27: ...DEIMOS BT UL Ver 07 27 D811419_07...

Page 28: ......

Reviews: