BFT DEIMOS BT KIT UL Installation And User Manual Download Page 15

To connect the photocells refer to the diagram in fig. 19  taking into account the 

number of pairs used: 1 pair box 1C, 2 pairs box 2C. The control unit performs 

the test of 2 safety devices. The additional devices must be equipped with 

internal self-diagnosis and connected in series. If photocells are not used, 

leave the jumpers aligned between terminal 21/23, and between terminal 

21/24 of the 

QSC D UL 

board. The connection of the infrared rubber skirt 

must be performed in the same way as for the photocells, i.e. by energizing 

the transmitter from terminal 16/17 and the receiver from terminal 12/13.

14) PROGRAMMING

The control panel provided with a microprocessor is supplied with function 
parameters preset by the manufacturer, suitable for standard installations. The 
predefined parameters can be altered by means of either the incorporated 
display programmer or 

universal palmtop programmer

.

In the case where programming is carried out by means of 

universal palmtop 

programmer

,  carefully  read  the  instructions  relating  to 

universal  palmtop 

programmer

, and proceed in the following way.

Connect the 

universal palmtop programmer

 to the control unit through the 

UNIFLAT and UNIDA accessories (See fig. 17). The 

QSC-D UL

 control unit 

does not supply the 

universal palmtop programmer

 with power, and therefore 

requires an appropriate supply unit.
Enter the “CONTROL UNITS” menu, and the “PARAMETERS” submenu, then 
scroll the display screenfuls using the up/down arrows to set the numerical 
values of the parameters listed below.
For the function logics, refer to the “LOGIC” submenu.
In the case where programming is carried out by means of the incorporated 
programmer, refer to Fig. A and B and to the paragraph on “Configuration”.

 

N.B.: The QSC-D UL control unit cannot supply the 

universal palmtop 

programmer

 with power.

 

15) CONFIGURATION

The  display  programmer  is  used  to  set  all  the 

QSC-D  UL

  control  panel 

functions.

The programmer is provided with three pushbuttons for menu scrolling and 

function parameter configuration:  

+

     menu scrolling/value increment key 

     menu scrolling/value reduction key

OK

  Enter (confirm) key

The simultaneous pressure of the + and - keys is used to exit the active 

menu and move to the preceding menu.  

The modifications made are only set if the OK key is subsequently pres-

sed.

When the OK key is pressed for the first time, the programming mode is entered.     

The following pieces of information appear on the display at first:
-    Control unit software version.
-    Number  of  total  manoeuvres  carried  out  (the  value  is  expressed  in 

hundreds, therefore the  display constantly shows 0000 during the first 
hundred manoeuvres).

-    Number of manoeuvres carried out since the latest maintenance opera-

tion (the value is expressed in hundreds, therefore the display constantly 
shows 0000 during the first hundred manoeuvres).

-    Number of memorised radio control devices.
When the OK key is pressed during the initial presentation phase, the first 
menu can be accessed directly.
Here follows a list of the main menus and the respective submenus available.
The predefined parameter is shown between square brackets [ 0 ].
The writing appearing on the display is indicated between round brackets.
Refer to Figures A and B for the configuration procedure.

15.1) Parameters menu
-   Automatic Closing Time (

TCA

) [ 10s ]

  Set  the  numerical  value  of  the  automatic  closing  time  from  3  to  120 

seconds. 

-   Opening Motor torque (

op. t

) [ 80% ]

  Set the numerical value of the motor torque between 1% and 99%.

-   Closing Motor torque (

cls. t

) [ 80% ]

  Set the numerical value of the motor torque between 1% and 99%.

-   Slow-down opening motor torque (

op. t slow

) [ 50% ]

 

(parameters 

 address 8)

  Set the numerical value of the motor torque between 1% and 99%.

-   Slow-down closing motor torque (

cls. t slow

) [ 50% ]

 

(Advanced parameters 

 address 9)

  Set the numerical value of the motor torque between 1% and 99%.

Fast Opening Time (

op. speed. time

) [ 15 s. ]

 

(Advanced parameters 

 address 6)

  Set the time ato normal opening speed (not slowed down), ranging from 

1 second to 2 mins. 

Fast Closing Time (

cls. speed. time

) [ 15 s. ]

 

(Advanced parameters 

 address 7)

  Set the time to normal closing speed (not slowed down), ranging from 1 

second to 2 mins. 

 

Note:

 The slow-down time, on closing and on opening, is obtained by 

timing one manoeuvre, and setting a lower value within this parameter. If, 
for example, one manoeuvre lasts 15 seconds, set “normal speed time” 
to 12s to obtain 3s of slow-down time.

Slow-down speed (

slov speed

) [ 0 ]

 

(Advanced parameters 

 address 5)

  Set the slow-down speed by choosing from one of the following values:
  0 – slow down disabled
  1 – slow down at 50% of normal speed
  2 – slow down at 33% of normal speed
  3 – slow down at 25% of normal speed

-   Zone (

zone

) [ 0 ] 

(Advanced parameters 

 address 1)

  Set the zone number between a minimum value of 0 and a maximum 

value of 127. See paragraph on “Serial connection”.

15.2) MENU LOGIQUES (

logic

)

-     TCA  (

TCA

) [ OFF ]

ON  Activates automatic closing
OFF  Excludes automatic closing 

-     3 Steps  (

3 step

)  [ OFF ]

ON  Enables 3-step logic. A Start impulse has the following effects:
 

door closed:   opens 

 

on opening:    stops and enters TCA (if configured)

 

door open:     closes

 

on closing:    stops and reopens

OFF  Enables 4-step logic. A Start impulse has the following effects:
 

door closed:   opens

 

on opening:    stops and enters TCA (if configured)

 

door open:     closes 

 

on closing:    stops and does not enter TCA (stop)

 

after stopping:  opens

-     Impulse lock (

ibl open

) [ OFF ]

ON  The Start impulse has no effect during the opening phase.
OFF  The Start impulse becomes effective during the opening or closing 

phase. 

-     Photocells on opening (

photc. open

) [ OFF ]

ON:   In case of obscuring, this excludes photocell operation on opening.   

During the closing phase, it immediately reverses the motion.

OFF:  In case of obscuring, the photocells are active both on opening and 

on closing. When a photocell is obscured on closing, it reverses the 
motion only after the photocell is disengaged. 

-     Photocell test (

test phot

) [ OFF ] 

(Advanced logics 

 address 14)

 

ON  Activates photocell check 
OFF  Deactivates photocell check 
 

If this setting is not activated (OFF), it inhibits the photocell checking 
function, allowing connection of devices not provided with additional 
checking contact. 

-     Prealarm  (

preal

) [ OFF ]

ON  The blinker comes on about 3s before the motors start.
OFF   The blinker comes on at the same time as the motors start

-    Hold-to-run control (

hold-to-run

) [ OFF ]

ON  Hold-to-run operation: the manoeuvre continues as long as the control 

key is kept pressed.(OPEN-CLOSE)

OFF  Impulse operation, according to the 3 or 4 step logic.

-    Start-Close

 

selection (

start - close

) [ OFF ]

ON  The input between the two terminals 21-22  acts as close
OFF  The input between the two terminals 21-22  acts as start

-      Fixed code (

fixed code

) [ OFF ]

 

(Advanced logics 

 address 13)

ON  The  receiver  is  configured  for  operation  in  fixed-code  mode,  see 

paragraph on “Radio Transmitter Cloning”.

OFF  The  receiver  is  configured  for  operation  in  rolling-code  mode,  see 

paragraph on “Radio Transmitter Cloning”.

-      Radio transmitter programming  (

radio prog

) [ ON ]

 

(Advanced logics 

 address 15)

ON  This enables transmitter storage via radio:
 

1 – First press the hidden key (P1) and then the normal key (T1, T2, 
T3 or T4) of a transmitter already  memorised in standard mode by 
means of the radio menu.

 

2 – Within 10s press the hidden key (P1) and the normal key (T1, T2, 
T3 or T4) of a transmitter to be memorised.

 

The receiver exits the programming mode after 10s, other new tran-
smitters can be entered before the end of this time. 

 

This mode does not require access to the control panel.

INSTALLATION MANUAL

ENGLISH

DEIMOS BT UL Ver. 07 - 

15

D811419_07

Summary of Contents for DEIMOS BT KIT UL

Page 1: ...Tel int 39 0445 696533 Fax 0445 696522 Internet www bft it E mail sales bft it ATTUATORE IN BASSA TENSIONE PER CANCELLI SCORREVOLI A CREMAGLIERA LOW VOLTAGE ACTUATOR FOR RACK SLIDING GATES DEIMOS BT U...

Page 2: ...ll automazione avvalersidipersonalequalificato installatore Annualmente far controllare l automazione da personale qualificato L entrata riservata ai veicoli Prevedere un entrata separata per i pedoni...

Page 3: ...y branches or shrubs Foranydirectassistancetotheautomationsystem requesttheassistance of a qualified technician installer Have qualified personnel check the automation system once a year Entrance is r...

Page 4: ...ono disponibili i seguenti accessori opzionali Kit batteria tampone mod SBBAT Incorporabile nell attuatore consente il funzionamento dell automazione anche se manca per un breve periodo l alimentazion...

Page 5: ...del l uso del cancello e non risolve problemi dovuti a difetti e deficienze di installazione o di mancata manutenzione del cancello stesso Togliere il prodotto dall imballo e verificarne l integrit S...

Page 6: ...ci CEI 64 8 IEC364 armonizzazione HD384 ed altre norme nazionali ATTENZIONE Per il collegamento alla rete utilizzare cavo multipolare di sezione minima 3x16AWG e del tipo previsto dalle normative vige...

Page 7: ...i rallentamento in chiusura e in apertura si ottiene cro nometrando la durata di una manovra ed impostando un valore minore in questo parametro Se ad esempio la durata di una manovra di 15 secondi imp...

Page 8: ...UTOset Consente di effettuare il settaggio automatico della Coppia motori ATTENZIONE L operazione di autosettaggio va effettuata da finecorsa di chiusura Se si prova ad effettuare l Autoset in una pos...

Page 9: ...la manopola non viene riportata nella posizione iniziale azionamento motorizzato Per ripristinare il comando motorizzato ruotare la manopola in senso antiorario per tutta la sua corsa e togliere la ch...

Page 10: ...M P OK OK PM P B M ON OFF ML P OK OK AMB 11M ON OFF M P OK OK OK P R T LMPK OK OK P R T LMPK AF OK OK P T P OK OK 8MLC P OK OK P A P OK OK P A AF P OK 1R P ON OFF M P OK OK MM ON OFF M P OK Fig A OK P...

Page 11: ...M L QAMQRM PGJ QAG R QRM BCQGBCP RM 0 CEEG MENU RADIO AGGIUNGI Consente di aggiungere un tasto di un radiocomando nella memoria della ricevente dopo la memorizzazione restituisce numero del trasmettit...

Page 12: ...he drive relays and safety devices photocells and safety edge before carrying out any manoeuvre M Motor R Reduction gear with worm screw and wheel F Electromechanical limit switch unit P Pinion S Rele...

Page 13: ...laced in order to fix the reduction gear unit fig 3 If the sliding track is already there digging must be partly carried out in the track foundation casting This way should the track foundation castin...

Page 14: ...able having a minimum cross section of 3x16 AWG and complying with the current standards For example if the cable is not protected it must be at least equal to H07 RN F whereas if it is protected it m...

Page 15: ...otor torque between 1 and 99 Slow down closing motor torque cls t slow 50 Advanced parameters address 9 Set the numerical value of the motor torque between 1 and 99 Fast Opening Time op speed time 15...

Page 16: ...rque reached during some of the manoeuvres carried out in the course of installation and if necessary set a value about 15 20 percent points higher in the parameter menu 15 7 AUTOSET MENU autoset Allo...

Page 17: ...erned In the case where a release knob with personalised key is fitted fig 18 proceed as follows Insert the personalised key in the lock and rotate the key anti clockwise Grip the release knob and rot...

Page 18: ...1 max 99 Fast opening time value expressed in seconds default 15 15s min 1 1s max 2 2 min Fast closing time value expressed in seconds default 15 15s min 1 1s max 2 2 min Slow down numerical value de...

Page 19: ...adio control device QR PR FGBBCL SRRML PCJC QC BCQGPCB SRRML 0 0 OK OK OK 0 1 R 06 OK OK OK OK RADIO MENU ADD Allows you to add one key of a radio control device to the receiver memory after storage i...

Page 20: ...8 249 mm 5 1 131mm 4 6 118 mm 6 2 160mm 10 4 265 mm 4 8 122 mm 1 9 50 mm 0 8 2 2 m m 1 7 4 3 m m Min 3 9 100mm Z14 Z 1 4 p 2 2 5 6 m m 0 9 25mm Min 2 9 75mm AXI PIGNON RITZELACHSE CENTRO PINON CENTRO...

Page 21: ...m 1 2 32mm 1 1 28mm 0 8 22mm 0 8 22mm DX SX Min 1 9 50mm NO OK push the control button or use the emergency relase In the event a person is trapped under the door Always keep a closing door within sig...

Page 22: ...2 S 24V 25W Max M 19 20 NO NO FAULT COM PED 21 22 23 24 25 26 COM 5 NC SWC NC SWO 24V JP2 JP3 JP1 0V 1 2 3 4 6 7 9 10 12 13 11 8 14 15 16 17 18 ANT Grigio Grey Gris Grau Gris Cinzento Grigio Grey Gris...

Page 23: ...te Contactos Contatos Contatti Contacts Contacts Kontakte Contactos Contatos 1 3 4 1 2 2 3 4 P1 P1 T1 Led T2 P1 P1 T1 T2 T3 T4 P1 P1 T1 Led T2 P1 P1 T1 T2 T3 T4 P1 P1 UNIFLAT UNIFLAT UNIMITTO UNITRC U...

Page 24: ...24 21 35 36 13 12 13 12 13 12 13 12 13 12 13 12 13 12 24 21 35 36 38 39 37 21 18 40 21 18 37 Rx 2 Rx 1 Tx 2 Tx 1 1 2 3 4 5 1 2 1 2 1 2 3 4 Rx 4 Rx 3 Tx 4 Tx 3 1 2 3 4 5 5 5 1 2 1 2 1 2 3 4 Rx 3 Tx 3...

Page 25: ...SCS1 SCS1 Max 250m TX1 TX2 RX1 RX2 TX1 TX2 RX1 RX2 TX1 TX2 RX1 RX2 SCS1 QSC D UL Fig 20A TX1 TX2 RX1 RX2 35 36 37 38 35 36 37 38 STOP SWO1 CC1 21 22 23 24 7 25 26 NC PHOT NC NC SWC1 6 NC SWO2 CC2 21 2...

Page 26: ...26 DEIMOS BT UL Ver 07 D811419_07...

Page 27: ...DEIMOS BT UL Ver 07 27 D811419_07...

Page 28: ......

Reviews: