Transport, Installation and Connection
4-10
4.10.2
Terminal diagram
Occupancy of socket / plug
PIN
Internal connection
AC/DC
Colours of BFI special cable
KW6
1
White
2
Brown
3
Pink
4
+ 24V
DC
Green
5
0 V
Yellow
6
Output 4-20 mA
Gray
7
Switch over channel 2
with external 24 V DC
Blue
Not used
Red
Connection of standard compact flame controller with special cable KW6
Internal
External
Con-
tact
Core colour Function
Burner
control
mA
display
Power supply
1
White
Flame relay lead
x
2
Brown
Flame relay Flame ON
x
3
Pink
Flame relay Flame OFF
x
4
Green
Power 24V DC
+24V DC/200mA
5
Yellow
Power supply GND
-
GND
6
Gray
Analogue (0/4 to 20
mA)
+
7
Blue
Switch over channel 2 with ex-
ternal 24 V DC
(x)
Red
Not used
3
4
5
6
1
2
7
Summary of Contents for CFC 100
Page 2: ......
Page 11: ...General aspects 1 7 1 8 Declaration of conformity ...
Page 20: ...Safety 2 8 ...
Page 24: ...Technical data 3 4 3 5 Block diagram CFC100 ...
Page 36: ...Transport Installation and Connection 4 12 ...
Page 40: ......
Page 42: ...Operation of the Compact Flame Controller 6 2 ...
Page 46: ...Failures 8 2 ...