Transport, Installation and Connection
4-6
The use of a
swivel mount
(optional, Part No.: 6590-9020-
01) allows adjustments to be carried out easily in order to
mechanically obtain the optimum observation point. The
compact flame controller is supplied complete with a
quick-installation flange. This guarantees quick and easy
removal of the compact flame controller. It has a purge air
connection whose special design prevents soiling of the
lens without the possibly dust-laden purge air being able
to damage the lens. If temperatures of over 50 °C occur at
the compact flame controller caused by the heat dissipa-
tion of the sight tube despite the inflow of cooling air, a
heat insulator
(optional, Part No.: 1598-0141-00) must be
employed. At pressurised firing installations, an additional
3-port shut-off device
(optional, Part No.: 1594-8831-00)
should be installed for the sake of safety. This prevents
an escape of hot gases after the removal of the compact
flame controller and provides additional cooling and purg-
ing of the installation.
The entire mechanical peripheral system can be supplied
by BFI Automation.
1
2
3
4
5
7
8
9
10
6
1 Harting plug
2 Special cable KW5
3 Compact Flame Con-
troller
4 Purge air connection
5 Purge air flange
6 Sight tube connec-
tion
7 Heating insulator
8 3-way-ball-valve
9 Double nipple
10 Swivel mount
Summary of Contents for CFC 100
Page 2: ......
Page 11: ...General aspects 1 7 1 8 Declaration of conformity ...
Page 20: ...Safety 2 8 ...
Page 24: ...Technical data 3 4 3 5 Block diagram CFC100 ...
Page 36: ...Transport Installation and Connection 4 12 ...
Page 40: ......
Page 42: ...Operation of the Compact Flame Controller 6 2 ...
Page 46: ...Failures 8 2 ...