Failures
8-1
8
Failures
Problem:
Display:
Cause:
Remedy:
No
Flame
ON s
ignal af-
ter the
burner was
started
No mA output signal
Yellow LED
OFF
Green LED
OFF
No data communication
Compact flame con-
troller not functioning
Check voltage supply
Replace compact flame controller
Check electrical connection
Flame signal (software)
low
Yellow LED
OFF
Flame signal too low
or below the starting
threshold
Inspect compact flame controller
Check flame, adjustment, sight tube
and lens
Check / set sensitivity and switching
thresholds
Flame signal (software)
above the starting thresh-
olds
Yellow LED OFF
Red LED ON (software)
Device or self-test
fault
Check fault memory
Possibly remove plug for 5 seconds
then start the burner again
Replace compact flame controller
Flame signal (software)
above the starting thresh-
olds
Yellow LED ON
Green LED ON
Relay contact or wir-
ing problem
Check fuse in relay output circuit
Check electrical connection
Burner fails
Flame signal (software)
drops. Below the shut-off
threshold, the flame relay
switched off.
No flame, weak flame
signal
Check flame
Inspect compact flame controller
Check alignment and lens
Check sensitivity setting
Check switching thresholds
Replace compact flame controller
Check electrical connection
Flame signal above shut-
off threshold
Yellow LED OFF
Device or self-test
fault
Check fault memory
Possibly remove plug for 5 seconds
then start the burner again
Replace compact flame controller
Summary of Contents for CFC 100
Page 2: ......
Page 11: ...General aspects 1 7 1 8 Declaration of conformity ...
Page 20: ...Safety 2 8 ...
Page 24: ...Technical data 3 4 3 5 Block diagram CFC100 ...
Page 36: ...Transport Installation and Connection 4 12 ...
Page 40: ......
Page 42: ...Operation of the Compact Flame Controller 6 2 ...
Page 46: ...Failures 8 2 ...