EIB Alarm Central Unit, surface-
mounted
75730010
Technical
Documentation
© Gebr.Berker 2005
Version: 18.08.2005
Page: 23 / 81
(Subject to prior change)
75730010.doc
Part 9
•
Configuration 5.1:
1 x safeguarding area (SA 1), separate.
1 x safeguarding area (SA 4), cascaded, i. e. the arming areas must be armed one by one,
e. g. office complexes, industrial buildings, sports halls, etc.
AA 1:
SA 1 (separate safeguarding area) can be armed by AA 1. In the event of an
alarm, the alarm indicators assigned to AA 1 will be activated. However, if AA 4 is
in the armed state alarms will be raised by AA 4.
AA 4:
SA 4 (cascaded safeguarding area) must only be armed by AA 4 after AA 1 has al-
ready been armed. When AA 4 is in the armed state, and in the event of an alarm,
no matter in which safeguarding areas, the alarm indicators assigned to AA 4 will
be activated.
When AA 4 is being disarmed subordinate AA 1 will still remain armed and must
be disarmed separately, if desired.
AA 1
AA 4
•
Configuration 5.2:
2 x safeguarding area (SA 1 and SA 2), separate.
1 x safeguarding area (SA 4), cascaded, i. e. the arming areas must be armed one by one,
e. g. office complexes, industrial buildings, sports halls, etc.
Same as configuration 5.1, however, in addition:
AA 2:
SA 2 (separate safeguarding area) can be armed by AA 2. In the event of an
alarm, the alarm indicators assigned to AA 2 will be activated. However, if AA 4 is
in the armed state alarms will be raised by AA 4.
AA 4 must only be armed after AA 1 and AA 2 have already been armed.
When AA 4 is being disarmed the subordinate arming areas (AA 1 and AA 2) will still
remain armed and must be disarmed separately, if desired.
AA 1
AA 4
AA 2
•
Configuration 5.3:
3 x safeguarding area (SA 1, SA 2 and SA 3), separate.
1 x safeguarding area (SA 4), cascaded, i. e. the arming areas must be armed one by one,
e. g. office complexes, industrial buildings, sports halls, etc.
Same as configuration 5.2, however, in addition:
AA 3:
SA 3 (separate safeguarding area) can be armed by AA 3. In the event of an
alarm, the alarm indicators assigned to AA 3 will be activated. However, if AA 4 is
in the armed state alarms will be raised by AA 4.
AA 4 may only be armed after AA 1, AA 2 and AA 3 have already been armed.
When AA 4 is being disarmed the subordinate arming areas (AA 1, AA 2 and AA 3)
will still remain armed and must be disarmed separately, if desired.
AA 1
AA 4
AA 2
AA 3