EIB Alarm Central Unit, surface-
mounted
75730010
Technical
Documentation
© Gebr.Berker 2005
Version: 18.08.2005
Page: 41 / 81
(Subject to prior change)
75730010.doc
Part 9
5.1.2 Triggering the display units (by the example of concealed info display unit 2.0 from version 2.x or later)
Through the info display unit, a great variety of information on the general EIB installation can be visualized. To en-
able info display unit 2.0 to issue information of the alarm central unit you must have parameterized a page in the ETS
plug-in of the display as "page function = alarm central unit display". When doing so, you will permanently assign
certain functions to the individual text lines and display keys.
Updating the display contents is event-controlled for this page function. Thus, the alarm central unit will update the
display texts automatically once any change of the system state (e. g. faults or alarms) occurs in an area.
In the armed state or in the "alarm" state, the display texts of the arming areas concerned will always be hidden.
Display window
function keys
A / B / C / D
"select"
"navigate"
line 1 (14 characters)
line 2 (14 characters)
line 3 (14 characters)
line 4
Text lines:
Line 1 will be addressed by the alarm central unit. For this purpose, a "line 1" ETS object used for the display is
enabled to which the alarm central unit sends the text to be issued. Thus, the identification text for the arming
areas or for the "fire detector" or "attack detector" areas parameterized from the ETS plug-in will be displayed in
this line, depending on which of these areas you have selected by the two function keys on the left.
Line 2 will also be addressed by the alarm central unit through the "line 2" ETS object. At this position, the alarm
central unit will issue the editable detector texts or, if no detectors are concerned, directly indicate the system
state of the area selected in line 1.
Line 3 will complete line 2, i. e. the detector states will be displayed if any detectors are concerned, or further
text messages will be issued. In the "disarmed after alarm" state, the exact time and date when the alarm was
raised will, among other things, be visualized at this position
(refer to "4.6 System states/"disarmed after alarm"
state", page 34)
.
Line 4 can be parameterized from the ETS plug-in of the info display unit through the "line 4 text" parameter. In
this line, you should 'name' the functions of the function keys below (refer to the description of the function keys
given later). Line 4 will always display the entered text in inverse form.