If the
Enable Test Event
is Disabled, the Control
panel will not send the Test call.
Enable Test Event
If this option is Enabled, the Con-
trol panel will generate the
Test event
in accordance
with the
First Test
and
Repeat test event
parameters.
If this option is Disabled (at default), the
Test event
will
be inhibited.
First Test
This programming field is for the date and
time of the first Test.
+
Subsequent Test calls depend on the
Repeat test
event
setting.
Repeat test event
This programming field is for the in-
terval between Test calls.
Initialize
If you are downloading a new Test setting to
the Control panel, you must select this button, other-
wise the new setting will be ignored.
+
If the entered date and time are prior to the current
date and time on the computer, the
Initialize
but-
ton will be inhibited. The Control Panel must be
connected to the PC via serial port or telephone.
n
Installer Maintenance
The
Installer Maintenance
section will allow you to
program the date and time of
Installer Maintenance Re-
quest signal
.
The
Installer Maintenance Request
will be signalled by the:
Ø
Installer Maintenance
event;
Ø
ON status of the
G
indicator on the keypad.
+
The Trouble indicator
G
signals various Trouble
events. The Trouble details can be found on the
LCD Keypads (in View Mode). If the trouble is re-
lated to an
Installer Maintenance
Request, the
relevant message will be shown (see the
Descrip-
tion
field in the
Installer Maintenance
section).
The Trouble signal generated by the
Installer Mainte-
nance Request
and
Installer Maintenance
will termi-
nate when:
Ø
the
Teleservice
page is downloaded;
Ø
the Date and Time of Installer Maintenance are pro-
grammed at the Keypad (refer to “Teleservice” in the
KEYPAD PROGRAMMING MANUAL).
To set up the
Installer Maintenance Request
— Enable
the
Maintenance Request
option and set the Date and
Time, as follows.
Date
Enter the date of the
Installer Maintenance Re-
quest
signal.
Time
Enter the time of
Installer Maintenance Request
signal.
Description
Edit the message that will be shown on
Keypad (in View Mode) when an
Installer Maintenance
Request
is received.
n
Central Station Maintenance
The
Central Station Maintenance
section will allow
you to program the date and time of the
Monitoring
Maintenance Request signal.
The
Monitoring Maintenance Request
will be signalled
by the :
Ø
Central station maintenance
event;
Ø
ON status of
G
indicator on the keypad.
+
The Trouble
G
indicator signals various Trouble
events. The Trouble details can be found on the
LCD Keypads (in View Mode). If the trouble is re-
lated to a Monitoring Maintenance Request, the
relevant message will be shown (refer to the De-
scription field in the
Central station maintenance
section).
The Trouble signal generated by the
Central station
maintenance request
and the
Central station mainte-
nance
event will terminate when:
58
Figure 42
Teleservice page