The Expander Outputs are 0.15 A Open-Collectors.
The terminals for these Outputs are OC1, OC2, OC3,
OC4, OC5 and OC6.
A
The IMQ SECURITY SYSTEM Approval applies
only when the Expander Open-Collector Outputs
are interfaced with relays (installed inside the Ex-
pander boxes).
The Output Expander Buzzer
98
can be connected to
the terminal
[OC6]
via jumper
99
:
Ø
1
ooo
3 = buzzer OFF (at default):
Ø
1
//o
3 = the buzzer will sound when the terminal
[OC6] opens;
Ø
1
o//
3 = the buzzer will sound when the terminal
[OC6] closes to Negative.
The Control Panel Outputs and Expander Outputs can
be associated with Events that activate signalling de-
vices (Sirens, Flashers, etc.), or used to provide Oper-
ating/Trouble status and device control signals. They
can also be used to turn ON/OFF electrical appliances
at the Keypad or via telephone (Heating, Garden sprin-
klers, etc.).
The
Outputs
page will allow you to program the Control
Panel and Expander Output parameters, as follows.
The table on the left side of the
Outputs
page shows
the Outputs. The number of available Outputs depends
on the system (refer to “Configuration”). The following
information will be shown for each Output.
No.
This field shows the Output ID number, used in
some parts of the application, instead of the Output De-
scription (refer to “Description”).
Position
This field shows the
Description
of the Out-
put placement. This label can be edited on the
Output
Expanders
page.
Device
This field shows the Address of the Output place-
ment (Control Panel Outputs are indicated by a hyphen).
Ter.
This field shows the Output terminal tag:
Ø
RL1
= +N1, +A1, C1-NC1-NA1
Ø
RL2
= +N2, +A2, C2-NC2-NA2
Ø
RL3
= +N3, +A3, C3-NC3-NA3
Description
This editable field (16 characters) is for
the Output label (e.g. the detector placement or the
name of the Key User).
The
Parameters
on the right side of the
Outputs
page
can be programmed as follows.
Type
The Output can be programmed as either Mono-
stable (
M
) or Bistable (
B
).
Pol.
The Output can be programmed as either
Normally Closed (
NC
) or Normally Open (
NO
).
n
Type
Bistable
This type of Output will activate when AT
LEAST ONE of its associated Events occurs, and will
stop when ALL of its associated Events end.
A
The IMQ SECURITY SYSTEM Approval applies
only when the Outputs — used for Alarm device
activation — are
MONOSTABLE
.
Monostable
ThistypeofOutputwillactivatewhenATLEAST
ONEofitsassociatedEventsoccurs,andwillstopwhenthepro-
grammed
ON Time
expires (see “ON Time” below).
n
Polarity
This programming field will allow you to program the
Output standby polarity .
Normally Open
The electrical state during standby is:
[+N] terminals open; Positive signal (13.8V) on the [+A]
terminals; [C] terminals closed to their respective [NO]
terminals; [NC] and [OC] terminals open.
KYO 300-KYO100
PROGRAMMING
45
Figure 31
Outputs page