AC Power and Grounding
2-10
Installation, SPM, Maintenance, and Troubleshooting Supplement
Using an Ideal 61-035 Circuit Tester
(or Equivalent)
2
Follow these steps to use an Ideal 61-035 Circuit Tester or its equivalent:
1.
Plug the circuit tester into the outlet that you want to test.
If the circuit is properly grounded, the yellow and white lights on the tester
turn on.
2.
Unplug the circuit tester.
Using a Volt-Ohm Milliammeter (VOM)
2
Follow these steps to use a VOM:
1.
Set the VOM to the lowest scale on which you can read
130 V AC.
2.
Measure the AC outlet voltages. See Figure 2-2 on page 2-11.
■
Phase to ground should be 110 to 125 V AC.
■
Neutral to ground should be less than 1 V AC.
■
Phase to neutral should be 110 to 125 V AC.