6.2. Solenoid valve test function
Pressing the >>Test<< button will control the solenoid valve and switches on 3 cycles for a length of 2 seconds.
Solenoid valve opened
→
Red LED off
→
complete purge air exits
Solenoid valve closed
→
Red LED on
→
only measuring gas exits
Test
Power
+10
10
+5
20
0
30
Value
35 45 55
°C
°C
-5 -15 -26
P
ressure
D
ew
P
oint
∆
∆
...
...
Press and hold the >>Test<< button for 3 seconds
Activation is displayed (all green LEDs flash)
Release the >>Test<< button
valve switches for 3 cycles
The system subsequently returns to normal operating
mode.
6.3. Carrying out settings (set-up mode)
The software must be initially unlocked to be able to acquire settings. The unlocking is executed by simultaneously pressing
the >>Value<< + >>Test<< buttons: All green LEDs flash to confirm activation.
You now have 10 seconds to acquire the settings. Every actuation of a button during this time span will result in the time
span being available again for the complete duration.
Test
Power
+10
10
+5
20
0
30
Value
35 45 55
°C
°C
-5 -15 -26
P
ressure
D
ew
P
oint
∆
∆
...
...
Press >>Test<< + Taste >>Value<< button for 3 seconds
Activation is displayed (all green LEDs flash)
Release both buttons: Setup mode is activated
Acquire amendments / settings
All settings apply until they are amended. Settings can be acquired via the >Value<< and >>Test<< buttons.
6.3.1. Amend the
operating mode
6.3.2. Altering the values
Test
Power
+10
10
+5
20
0
30
Value
35 45 55
°C
°C
-5 -15 -26
P
ressure
D
ew
P
oint
∆
∆
...
...
Press the >>Test<< button.
The power LED is lit
permanently:
Constant mode
Power LED flashes
(2 second cycle on-off)
Dynamic mode
Test
Power
+10
10
+5
20
0
30
Value
35 45 55
°C
°C
-5 -15 -26
P
ressure
D
ew
P
oint
∆
∆
...
...
Press the >>Value<< button
1 value LED lights up:
35K / -5 °C (example)
Test
Power
+10
10
+5
20
0
30
Value
35 45 55
°C
°C
-5 -15 -26
P
ressure
D
ew
P
oint
∆
∆
...
...
Press the >>Value<< button
again
2 value LEDs light up:
Intermediate value
40K / -10 °C (example)
Once the action or amendment has been finalised and no button has been pressed for a time period of 10 seconds, then
the confirmation for finalising the action / acquisition of the amended values is executed: All green value LEDs flash. The
system then transfers into normal mode and is controlled on the basis of the prescribed settings.