4.2 Installation Procedure
Fig 4 illustrates the instrument installation
procedure.
a. Remove the instrument terminal cover by
unscrewing the two captive 'A' screws.
b. Mount the instrument on a flat surface and
secure with screws or bolts through the two
'B' holes. Alternatively use one of the pipe or
stem mounting kits described in sections 8.7
and 8.8
c. Remove the temporary dust seals from the
three cable entries and install the required
glands, conduit fittings or blanking plugs.
Note: the temporary dust seals do not
provide IP66 protection.
d. Connect the field wiring to the terminals as
shown in Fig 5.
e. Replace the instrument terminal cover and
evenly tighten the two 'A' screws.
Fig 4 BA524D installation procedure
4.3 EMC
The BA524D complies with the requirements of the
European EMC Directive 89/336/EEC. For
specified immunity all wiring should be in screened
twisted pairs.
Additional immunity may be obtained by
connecting the BA524D earth terminal to a local
earth, or to an earthed cable screen.
Fig 5 Dimensions and terminal connections
5