8.2.3 Alarm enable: EnbL
This function allows the alarm to be enabled or
disabled without altering any of the alarm
parameters. To check or change the function
select 'EnbL' from the alarm menu and press
P
which will reveal the current setting. The function
can be changed by pressing the
Up
or
Down
button
followed by the
E
button to return to the alarm
menu.
8.2.4 Setpoint adjustment: SP1 and SP2
The setpoint of each alarm may be positioned
anywhere between -19999 and 19999 providing
this corresponds to an input current between 3.8
and 20.2mA. e.g. If the indicator has been
calibrated to display 0 with 4mA input and 10000
with 20mA input, the two alarm setpoints may be
positioned anywhere between -125 and 10125.
To adjust the setpoint select 'SP1' or 'SP2' from the
alarm menu and press
P
which will reveal the
existing alarm setpoint. Each digit of the setpoint
can be adjusted using the
Up
and
Down
push-buttons, and the
P
button to move to the next
digit. When the required setpoint has been entered
press
E
to return to the alarm menu.
17