BEKA BA524D Manual Download Page 22

The selected break-point can be changed using the

Up

 and 

Down

 buttons.  When the required

break-point has been selected press 

P

.  Set the

indicator input current to the exact value at which
the break-point is to occur, and adjust the indicator
display using the 

Up

 and 

Down

 buttons and 

P

 to

move between digits.  When the required display
has been set, press 

to enter the information and

return to the sub-menu from which another
break-point  can be selected.   

Repeat this procedure for each break-point, and
then return to the main menu by pressing 

twice.

8.3.2  Calibration using internal references

This function enables the break-points to be
adjusted without the need for an accurate external
current source.  Throughout calibration the
indicator input current may be any value between 4
and 20mA.

The accuracy of this method depends upon the
accuracy of the internal references which should be
calibrated periodically against a traceable external
current source with a resolution of at least 0.4µA.   
See section 5.7.2 

The number of break-points required should first be
entered using the Add and dEL  functions.  In both
these functions the indicator initially displays the
current break-point and the total number of
break-points being used.  e.g.

                       

5              13

                   current                total number  of
                break-point               break-points

  

Display

      Description of function

'Add'

Add a break-point

Adds a new break-point before the
displayed break-point.  The calibration
of existing break-points is not changed,
but the identification number of
subsequent break-points is increased by
one.

'dEL'

Remove a break-point

Removes the displayed break-point and
joins the preceding break-point to the
following break-point with a straight line.
 The identification of subsequent
break-points is decreased by one.

  

Display

      Description of function

'InPut' Defines the current at which

break-point occurs

Enables the required current at each
break-point to be defined without having
to input an accurate input current to the
indicator.

'diSP'

Defines display at break-point

Enables the indicator display at each
break-point to be defined.

Select 'SEt' from the main menu and press 

P

 once

to enter the 'Add' function, and again  to reveal the
current and total number of break-points.   Each
subsequent operation of the

  P

  push-button will

introduce an additional break-point.  When adding
a break-point to a calibrated indicator, the insertion
position can be selected using the 

Up

 and 

Down

push-buttons.    

The delete break-point function 'dEL' operates in a
similar manner to the 'Add' function described
above.

When the required number of break-points has
been entered, return to the sub-menu by pressing

E.  

The indicator will display 'Add' or 'dEL'

depending upon the last function used.  The
required indicator display at each break-point can
now be entered, followed by the input current at
which each break-point occurs.  

To enter the required display at any break-point
select 'diSP' from the sub-menu and press 

P

 which

will select the first break-point '0  n', where 'n' is the
total number of break-points selected.     The
selected break-point can be changed using the 

Up

and 

Down

 buttons.  When the required break-point

has been selected  press 

P

  to reveal 

the existing display.  Using the 

Up

 and 

Down

buttons and 

P

 to move between digits set the

revised display.  Press 

to return to the sub-menu

from which another break-point  can be selected.   
Repeat this procedure for all the break-point
displays to be changed, and then return to the
'diSP' prompt in the sub-menu by pressing

 E.

To enter the input current at which each
break-point occurs select 'InPut' from the sub-menu
 and press 

P

  which will select the first break-point

'0  n'.   The selected break-point can be changed
using the 

Up

 and 

Down

 buttons.  When the

required break-point has been selected, press 

P

  to

reveal the input current at which the break-point
occurs.   Using the 

Up

 and 

Down

 buttons and  

P

  to

22

Summary of Contents for BA524D

Page 1: ...BA524D loop powered 4 digit field mounting indicator Issue 4 3rd December 2003...

Page 2: ...7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Customer comments 8 Accessories 8 1 Units of measurem...

Page 3: ...l converter Fig 1 Simplified block diagram of BA524D Each time a 4 20mA current is applied to the instrument initialisation is performed After a short delay the following display sequence occurs 1 8 8...

Page 4: ...tput is greater than the sum of voltage drops introduced by the BA524D and the cable resistance Fig 3 Remote indication 4 INSTALLATION 4 1 Location The BA524D indicator is housed in a robust IP66 glas...

Page 5: ...ll the required glands conduit fittings or blanking plugs Note the temporary dust seals do not provide IP66 protection d Connect the field wiring to the terminals as shown in Fig 5 e Replace the instr...

Page 6: ...parameter root to be displayed If an incor rect code is entered the indicator will return to the display mode Once within the menu the required parameter can be reached by scrolling through the main...

Page 7: ...ction 50 or 60Hz may be selected This function must be set before the instrument is calibrated as it affects the indicator display See section 5 7 1 rEF Calibration of internal references The instrume...

Page 8: ...have been adjusted press E to enter the new zero The indicator will display Ent for a few seconds while the information is being stored in memory and will then return to the ZErO prompt To adjust the...

Page 9: ...tor to 20 000mA and again press P The indicator will display Ent when the 20mA reference has been updated and will then return to the 020A prompt Two operations of the E button will return the indicat...

Page 10: ...10...

Page 11: ...display the input current as a percentage of span when the P push button is operated Step 1 Connect indicator to calibrator Connect the indicator to an accurate external current source Terminal 1 posi...

Page 12: ...erences As in 7 1 the BA524D is required to display 50 0 with a 4mA input 1050 0 with a 20mA input from a linear transducer Maximum display resolution is required the frequency of the mains supply is...

Page 13: ...ng completion of calibration return to the display mode by pressing E 7 MAINTENANCE 7 1 Fault finding during commissioning If a BA524D fails to function during commissioning the following procedure sh...

Page 14: ...s also unscrew the two C screws securing the buttons and un plug the five way connector Finally unscrew all four D screws identified in Fig 4 and carefully lift off the front of the instrument The ins...

Page 15: ...hanumeric characters 10mm high or 1 row of 11 alphanumeric characters 7mm high or 2 rows of 18 alphanumeric characters 5mm high 8 2 Alarms The BA524D can be supplied with two solid state single pole a...

Page 16: ...Alarm enable Enables or disables the alarm function without changing the alarm parameters See section 8 2 3 SP1 Alarm setpoint 1 Adjusts the alarm setpoint The alarm is activated when the indicator d...

Page 17: ...arm may be positioned anywhere between 19999 and 19999 providing this corresponds to an input current between 3 8 and 20 2mA e g If the indicator has been calibrated to display 0 with 4mA input and 10...

Page 18: ...et at 9000 and hysteresis of 200 will perform as follows High alarm will be activated when display equals or exceeds 9000 but will not reset until the display falls below 8800 8 2 8 Alarm delay dELA T...

Page 19: ...urity code allowing direct access to the setpoints by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with this function disabled and the security code set to 000...

Page 20: ...lumetric units by filling the tank with known incremental volumes and calibrating the indicator to display the sum of the increments at each break point The number of break points required should firs...

Page 21: ...21...

Page 22: ...oint occurs Enables the required current at each break point to be defined without having to input an accurate input current to the indicator diSP Defines display at break point Enables the indicator...

Page 23: ...ayed 8 5 Display backlight The BA524D can be supplied with LED backlighting to improve display contrast when the indicator is installed in poorly illuminated areas The backlight is electrically isolat...

Reviews: