BEKA BA524D Manual Download Page 4

3.  APPLICATIONS

3.1 Transmitter loops

The BA524D indicator may be connected in series
with any 4/20mA current loop that can tolerate the
1.1V drop required to operate the instrument, and
be calibrated to display the measured variable or
control signal in engineering units.

Fig 2 illustrates a typical application in which a
BA524D indicator is connected in series with a
2-wire transmitter.
  

Fig 2  BA524D in a transmitter loop

Considering the example shown in Fig 2, the sum
of the maximum voltage drops of all the compo-
nents in the loop must be less than the minimum
power supply voltage.

Minimum operating voltage of 2-wire Tx

10.0

Maximum voltage drop caused by controller

5.0

Maximum voltage drop caused by BA524D

1.1

Maximum voltage drop caused by cables

0.4

                                                                     _____

16.5V

Therefore at 20mA the power supply in this
example must have an output greater than 16.5V

3.2  Remote indication

A BA524D indicator may be driven from any
4/20mA signal to provide remote indication.  Fig 3
shows a typical application in which the output from
a gas analyser drives a BA524D.  Again it is neces-
sary to ensure that the voltage capability of the
4/20mA gas analyser output is greater than the
sum of voltage drops introduced by the BA524D
and the cable resistance.

Fig 3  Remote indication

4. INSTALLATION

4.1 Location

The BA524D indicator is housed in a robust IP66
glass reinforced polyester (GRP) enclosure incor-
porating an armoured glass window and stainless
steel fittings making it suitable for exterior mount-
ing in most industrial installations, including
off-shore and waste water treatment.  

The BA524D is surface mounting, but may be pipe
or stem mounted using the accessory kits
described in sections 8.7 and 8.8 of this manual.

The field terminals and the two mounting holes are
located in a separate compartment with a sealed
cover allowing the instrument to be installed
without exposing the display assembly.

 

Terminals

2 and 4 are internally joined and may be used for
linking the return 4/20mA wire - see Fig 2.
Similarly terminals 5 and 6 are internally joined and
may be used for linking cable screens.  The
BA524D earth terminal is connected to the internal
EMC filters.  For maximum radio frequency inter-
ference rejection this terminal should be connected
to a local earth, or to an earthed cable screen.

 

  To

prevent circulating currents, cable screens should
only be earthed at one point.

The BA524D enclosure is fitted with a bonding
plate to ensure electrical continuity between the
three conduit / cable entries.

4

Summary of Contents for BA524D

Page 1: ...BA524D loop powered 4 digit field mounting indicator Issue 4 3rd December 2003...

Page 2: ...7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Customer comments 8 Accessories 8 1 Units of measurem...

Page 3: ...l converter Fig 1 Simplified block diagram of BA524D Each time a 4 20mA current is applied to the instrument initialisation is performed After a short delay the following display sequence occurs 1 8 8...

Page 4: ...tput is greater than the sum of voltage drops introduced by the BA524D and the cable resistance Fig 3 Remote indication 4 INSTALLATION 4 1 Location The BA524D indicator is housed in a robust IP66 glas...

Page 5: ...ll the required glands conduit fittings or blanking plugs Note the temporary dust seals do not provide IP66 protection d Connect the field wiring to the terminals as shown in Fig 5 e Replace the instr...

Page 6: ...parameter root to be displayed If an incor rect code is entered the indicator will return to the display mode Once within the menu the required parameter can be reached by scrolling through the main...

Page 7: ...ction 50 or 60Hz may be selected This function must be set before the instrument is calibrated as it affects the indicator display See section 5 7 1 rEF Calibration of internal references The instrume...

Page 8: ...have been adjusted press E to enter the new zero The indicator will display Ent for a few seconds while the information is being stored in memory and will then return to the ZErO prompt To adjust the...

Page 9: ...tor to 20 000mA and again press P The indicator will display Ent when the 20mA reference has been updated and will then return to the 020A prompt Two operations of the E button will return the indicat...

Page 10: ...10...

Page 11: ...display the input current as a percentage of span when the P push button is operated Step 1 Connect indicator to calibrator Connect the indicator to an accurate external current source Terminal 1 posi...

Page 12: ...erences As in 7 1 the BA524D is required to display 50 0 with a 4mA input 1050 0 with a 20mA input from a linear transducer Maximum display resolution is required the frequency of the mains supply is...

Page 13: ...ng completion of calibration return to the display mode by pressing E 7 MAINTENANCE 7 1 Fault finding during commissioning If a BA524D fails to function during commissioning the following procedure sh...

Page 14: ...s also unscrew the two C screws securing the buttons and un plug the five way connector Finally unscrew all four D screws identified in Fig 4 and carefully lift off the front of the instrument The ins...

Page 15: ...hanumeric characters 10mm high or 1 row of 11 alphanumeric characters 7mm high or 2 rows of 18 alphanumeric characters 5mm high 8 2 Alarms The BA524D can be supplied with two solid state single pole a...

Page 16: ...Alarm enable Enables or disables the alarm function without changing the alarm parameters See section 8 2 3 SP1 Alarm setpoint 1 Adjusts the alarm setpoint The alarm is activated when the indicator d...

Page 17: ...arm may be positioned anywhere between 19999 and 19999 providing this corresponds to an input current between 3 8 and 20 2mA e g If the indicator has been calibrated to display 0 with 4mA input and 10...

Page 18: ...et at 9000 and hysteresis of 200 will perform as follows High alarm will be activated when display equals or exceeds 9000 but will not reset until the display falls below 8800 8 2 8 Alarm delay dELA T...

Page 19: ...urity code allowing direct access to the setpoints by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with this function disabled and the security code set to 000...

Page 20: ...lumetric units by filling the tank with known incremental volumes and calibrating the indicator to display the sum of the increments at each break point The number of break points required should firs...

Page 21: ...21...

Page 22: ...oint occurs Enables the required current at each break point to be defined without having to input an accurate input current to the indicator diSP Defines display at break point Enables the indicator...

Page 23: ...ayed 8 5 Display backlight The BA524D can be supplied with LED backlighting to improve display contrast when the indicator is installed in poorly illuminated areas The backlight is electrically isolat...

Reviews: