BEKA BA524D Manual Download Page 18

8.2.5  Alarm function:   HI.LO

Each alarm can be conditioned as a high or low
alarm.   To check or change the alarm function
select 'HI.LO' from the alarm menu and press 

P

 to

reveal the current setting.  The function can be
changed by pressing the 

Up

 or 

Down

 buttons

followed by the 

E

 button to return to the alarm

menu.

8.2.6  Alarm output status:   no.nc

This function allows the alarm output to be open or
closed in the alarm condition.  When deciding
which is required, care must be taken to ensure
that the alarm output is fail safe.    See Fig 8.

CAUTION

When the 4/20mA supply is removed
both alarm outputs will open
irrespective of conditioning.
Therefore for fail safe operation both
alarm outputs should be
programmed to be open in the alarm
condition.

To check or change the alarm output status select
'no.nc' from the alarm menu and press 

P

 reveal the

current setting.  The function can be changed by
pressing the 

Up

 or 

Down

 button followed by the 

E

button to return to the alarm menu.

8.2.7  Hysteresis:   HStr

During programming hysteresis is shown in the
units the indicator has been calibrated to display.
To adjust the hysteresis, select 'HStr' from the
alarm menu and press 

P

 which will reveal the

existing figure.  Each digit can be adjusted using
the 

Up

 and 

Down

 push-buttons, and the 

P

 button to

move to the next digit.  When the required
hysteresis has been entered, press 

to return to

the alarm menu.
e.g.  An indicator calibrated to display 0 to 10000,
with a high alarm set at 9000 and hysteresis of 200
will perform as follows:

High alarm will be activated when display
equals or exceeds 9000, but will not reset
until the display falls below 8800.

8.2.8  Alarm delay:   dELA

This function enables activation of the alarm output
to be delayed for a fixed time following the alarm
condition occurring.  The delay can be
programmed in 1 second increments up to 3600
seconds.  If a delay is not required zero should be
entered.  To adjust the delay select 'dELA' from the
alarm menu and press 

P

 which will reveal the

existing delay.  Each digit of the delay can be
adjusted using the 

Up

 and 

Down

 push-buttons, and

the 

P

  button to move to the next digit.  When the

required delay has been entered, press 

to return

to the alarm menu.

8.2.9  Alarm silence time:   SIL

This function is primarily intended for use in small
installations where the alarm output directly
operates an annunciator such as a sounder.  When
the alarm silence time is set to any figure other
than zero, the 

P

 push-button becomes an alarm

accept button.   After an alarm has occurred,
operating the 

P

  button will cause the alarm output

to revert to the non-alarm condition for the
programmed alarm silence time.  The display will
continue to indicate an alarm after it has been
accepted and silenced.   The alarm silence time
may be adjusted between 0 and 3600 seconds in 1
second increments.

To adjust the alarm silence time select 'SIL' from
the alarm menu and press 

P

  which will reveal the

existing time.  Each digit can be adjusted using the

Up

 and 

Down

 push-buttons, and the 

P

  button to

move to the next digit.  When the required time
has been entered press 

to return to the alarm

menu.

18

Summary of Contents for BA524D

Page 1: ...BA524D loop powered 4 digit field mounting indicator Issue 4 3rd December 2003...

Page 2: ...7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Customer comments 8 Accessories 8 1 Units of measurem...

Page 3: ...l converter Fig 1 Simplified block diagram of BA524D Each time a 4 20mA current is applied to the instrument initialisation is performed After a short delay the following display sequence occurs 1 8 8...

Page 4: ...tput is greater than the sum of voltage drops introduced by the BA524D and the cable resistance Fig 3 Remote indication 4 INSTALLATION 4 1 Location The BA524D indicator is housed in a robust IP66 glas...

Page 5: ...ll the required glands conduit fittings or blanking plugs Note the temporary dust seals do not provide IP66 protection d Connect the field wiring to the terminals as shown in Fig 5 e Replace the instr...

Page 6: ...parameter root to be displayed If an incor rect code is entered the indicator will return to the display mode Once within the menu the required parameter can be reached by scrolling through the main...

Page 7: ...ction 50 or 60Hz may be selected This function must be set before the instrument is calibrated as it affects the indicator display See section 5 7 1 rEF Calibration of internal references The instrume...

Page 8: ...have been adjusted press E to enter the new zero The indicator will display Ent for a few seconds while the information is being stored in memory and will then return to the ZErO prompt To adjust the...

Page 9: ...tor to 20 000mA and again press P The indicator will display Ent when the 20mA reference has been updated and will then return to the 020A prompt Two operations of the E button will return the indicat...

Page 10: ...10...

Page 11: ...display the input current as a percentage of span when the P push button is operated Step 1 Connect indicator to calibrator Connect the indicator to an accurate external current source Terminal 1 posi...

Page 12: ...erences As in 7 1 the BA524D is required to display 50 0 with a 4mA input 1050 0 with a 20mA input from a linear transducer Maximum display resolution is required the frequency of the mains supply is...

Page 13: ...ng completion of calibration return to the display mode by pressing E 7 MAINTENANCE 7 1 Fault finding during commissioning If a BA524D fails to function during commissioning the following procedure sh...

Page 14: ...s also unscrew the two C screws securing the buttons and un plug the five way connector Finally unscrew all four D screws identified in Fig 4 and carefully lift off the front of the instrument The ins...

Page 15: ...hanumeric characters 10mm high or 1 row of 11 alphanumeric characters 7mm high or 2 rows of 18 alphanumeric characters 5mm high 8 2 Alarms The BA524D can be supplied with two solid state single pole a...

Page 16: ...Alarm enable Enables or disables the alarm function without changing the alarm parameters See section 8 2 3 SP1 Alarm setpoint 1 Adjusts the alarm setpoint The alarm is activated when the indicator d...

Page 17: ...arm may be positioned anywhere between 19999 and 19999 providing this corresponds to an input current between 3 8 and 20 2mA e g If the indicator has been calibrated to display 0 with 4mA input and 10...

Page 18: ...et at 9000 and hysteresis of 200 will perform as follows High alarm will be activated when display equals or exceeds 9000 but will not reset until the display falls below 8800 8 2 8 Alarm delay dELA T...

Page 19: ...urity code allowing direct access to the setpoints by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with this function disabled and the security code set to 000...

Page 20: ...lumetric units by filling the tank with known incremental volumes and calibrating the indicator to display the sum of the increments at each break point The number of break points required should firs...

Page 21: ...21...

Page 22: ...oint occurs Enables the required current at each break point to be defined without having to input an accurate input current to the indicator diSP Defines display at break point Enables the indicator...

Page 23: ...ayed 8 5 Display backlight The BA524D can be supplied with LED backlighting to improve display contrast when the indicator is installed in poorly illuminated areas The backlight is electrically isolat...

Reviews: