BEKA BA524D Manual Download Page 12

Step 5

Define function of P push-button

Select 'C--P' from the main menu and
press 

to reveal the function of the

  P

button in the display mode.  Select
percentage 'PC' and return to the main
menu by pressing 

 E

Note:  Because an input current display
in milliamps is not required, it is not
necessary to calibrate the two internal
references.

Step 6

Position dummy decimal point

Scroll though the main menu until 'd.P.'
is displayed and then press

  P

.  Using

the 

Up

 and 

Down

 push-buttons position

the dummy decimal point in front of the
least significant digit.
Press 

E

 to return to the main menu.

Step 7

Calibrate the display

Scroll through the main menu until
'CAL' is displayed.  Press 

and the

indicator will request a 4mA input by
displaying  'ZErO'.  Set the input current
to 4.0000 ± 0.0004mA and press 

P

again which will reveal the existing zero
display.  Using the 

Up

Down

 and 

P

push-buttons enter the required zero
display of  -50.0  Press 

E

 to return to

the 'ZErO' prompt.

Press the

 Up 

push-button

 

and the

indicator will request a 20mA input by
displaying  'SPAn'.  Set the input
current to 20.0000 ± 0.0004mA and
again press 

P

  which will reveal the

existing display at 20mA.  Using the 

Up

,

Down

 and 

P

 push-buttons enter the

required display of  1050.0
Press 

E

 twice to return to the main

menu.

Step 8

Return to the display mode

Following completion of calibration
return to the display mode by pressing

'E

'.

6.2  Using the internal references

As in 7.1 the BA524D is required to display: 

-50.0

with a 4mA input

1050.0

with a 20mA input

from a linear transducer.  Maximum display
resolution is required, the frequency of the mains
supply is 50Hz and the existing security code is
1209.    In the operating mode the indicator is
required to display the input current in milliamps
when the 

P

 push-button is operated.

This example assumes that the internal references
have been routinely calibrated.

Step1

Enter the programming mode

With an input current between 4 and
20mA put the indicator in the
programming mode by simultaneously
pressing

  P

 and

 E.  

The indicator will

respond by displaying 'COdE'.  Press 

P

  

to clear this prompt and set the display
to the security code 1209 using the 

Up

,

Down

 and 

P

 push-buttons. Pressing 

E

will enter the code, and after a few
seconds during which the decimal
points will be scrolled, the first
parameter 'root' in the main menu will
be displayed. 

Step 2

Square root extractor

With 'root' displayed, press 

P

  which will

reveal the root extractor status.  The
root extractor can be turned on or off by
the 

Up

 or 

Down

 buttons.  Select 'OFF',

and press 

E

 to return to the main menu.

Step 3    Select frequency of maximum

rejection

Scroll though the main menu until
'Cond' is displayed.  Enter the
sub-menu by pressing 

P

 twice

 

and

select the 'FrE' function.  Using the 

Up

or 

Down

 buttons select '50',  and then

press 

E

  twice to return to the main

menu.

Step 4

Define function of

 P

 push-button

Select 'C--P' from the main menu and
press 

P

 to reveal the function of the

  P

button in the display mode.   Select
'4-20' and return to the main menu by
pressing 

E

.

12

Summary of Contents for BA524D

Page 1: ...BA524D loop powered 4 digit field mounting indicator Issue 4 3rd December 2003...

Page 2: ...7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Customer comments 8 Accessories 8 1 Units of measurem...

Page 3: ...l converter Fig 1 Simplified block diagram of BA524D Each time a 4 20mA current is applied to the instrument initialisation is performed After a short delay the following display sequence occurs 1 8 8...

Page 4: ...tput is greater than the sum of voltage drops introduced by the BA524D and the cable resistance Fig 3 Remote indication 4 INSTALLATION 4 1 Location The BA524D indicator is housed in a robust IP66 glas...

Page 5: ...ll the required glands conduit fittings or blanking plugs Note the temporary dust seals do not provide IP66 protection d Connect the field wiring to the terminals as shown in Fig 5 e Replace the instr...

Page 6: ...parameter root to be displayed If an incor rect code is entered the indicator will return to the display mode Once within the menu the required parameter can be reached by scrolling through the main...

Page 7: ...ction 50 or 60Hz may be selected This function must be set before the instrument is calibrated as it affects the indicator display See section 5 7 1 rEF Calibration of internal references The instrume...

Page 8: ...have been adjusted press E to enter the new zero The indicator will display Ent for a few seconds while the information is being stored in memory and will then return to the ZErO prompt To adjust the...

Page 9: ...tor to 20 000mA and again press P The indicator will display Ent when the 20mA reference has been updated and will then return to the 020A prompt Two operations of the E button will return the indicat...

Page 10: ...10...

Page 11: ...display the input current as a percentage of span when the P push button is operated Step 1 Connect indicator to calibrator Connect the indicator to an accurate external current source Terminal 1 posi...

Page 12: ...erences As in 7 1 the BA524D is required to display 50 0 with a 4mA input 1050 0 with a 20mA input from a linear transducer Maximum display resolution is required the frequency of the mains supply is...

Page 13: ...ng completion of calibration return to the display mode by pressing E 7 MAINTENANCE 7 1 Fault finding during commissioning If a BA524D fails to function during commissioning the following procedure sh...

Page 14: ...s also unscrew the two C screws securing the buttons and un plug the five way connector Finally unscrew all four D screws identified in Fig 4 and carefully lift off the front of the instrument The ins...

Page 15: ...hanumeric characters 10mm high or 1 row of 11 alphanumeric characters 7mm high or 2 rows of 18 alphanumeric characters 5mm high 8 2 Alarms The BA524D can be supplied with two solid state single pole a...

Page 16: ...Alarm enable Enables or disables the alarm function without changing the alarm parameters See section 8 2 3 SP1 Alarm setpoint 1 Adjusts the alarm setpoint The alarm is activated when the indicator d...

Page 17: ...arm may be positioned anywhere between 19999 and 19999 providing this corresponds to an input current between 3 8 and 20 2mA e g If the indicator has been calibrated to display 0 with 4mA input and 10...

Page 18: ...et at 9000 and hysteresis of 200 will perform as follows High alarm will be activated when display equals or exceeds 9000 but will not reset until the display falls below 8800 8 2 8 Alarm delay dELA T...

Page 19: ...urity code allowing direct access to the setpoints by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with this function disabled and the security code set to 000...

Page 20: ...lumetric units by filling the tank with known incremental volumes and calibrating the indicator to display the sum of the increments at each break point The number of break points required should firs...

Page 21: ...21...

Page 22: ...oint occurs Enables the required current at each break point to be defined without having to input an accurate input current to the indicator diSP Defines display at break point Enables the indicator...

Page 23: ...ayed 8 5 Display backlight The BA524D can be supplied with LED backlighting to improve display contrast when the indicator is installed in poorly illuminated areas The backlight is electrically isolat...

Reviews: