6.2.3  Access code for node configuration
          menu   ‘CodE’
Access  to  the  node  configuration  menu  may  be
protected  by  a  four  digit  security  code  which  must
be  entered  to  gain  access.    New  instruments  are
supplied  configured  with  the  default  code  0000
which 

disables 

this 

protection 

and 

allows

unrestricted access to the configuration menu.

To  enter  a  new  access  code  select  ‘CodE’  in  the
configuration  menu  by  operating  the 

  or 

button.      To  enter  the  function  press  P  which  will
reveal  the  current  access  code  with  one  digit
flashing. The code may be changed using the 

 or

  button  to  adjust  the  flashing  digit  and  the  P

button to move control to the next digit.  When the
required code has been selected, press E to enter
the selection and return to the ‘CodE’ prompt in the
configuration menu.    The revised access code will
be  activated  when  the  indicator  is  returned  to  the
display mode.

If  the  access  code  is  lost  please  contact  BEKA
associates.

Fig 4 Node configuration menu

6.3  Listener configuration menu
The  listener  configuration  menu  is  separated  into
three  sections,  ‘SCAn’,  ‘LISt’  and  ‘Edit’,  plus  three
housekeeping functions ‘CodE’, ‘tYPE’ and  ‘rESEt’
as shown in Fig 6.

‘SCAn’  is  the  simplest  method  of  configuration  if
the  fieldbus  Device  Address  and  Variable  Identity
of  the  data  to  be  displayed  by  the  BA448CF-F
listener are not known.

In  the  ‘SCAn’  function  pressing  the  P  button
causes  the  BA448CF-F  indicator  to  search  the
fieldbus  segment  to  which  it  is  connected  for  all
publishers.  Fig 5 shows how the indicator displays
the  hexadecimal  Device  Address  and  Variable
Identity associated with each publisher.

A  Publisher  is  a  device  that  places  it's  output
data  onto  the  bus  as  part  of  a  cyclical  pre-
determined data exchange schedule.

The  Device  Address  is  a  unique  address  that
identifies each fieldbus instrument connected to
the bus.

The  Variable  Identity  is  the  fieldbus  device
Data  Link  Connection  End  Point  (DLCEP)
which  identifies  each  Function  Block  output
(process  variable)  transmitted  by  a  fieldbus
device 

such 

as 

flow 

and 

temperature

transmitted by a fieldbus flowmeter.

The 

  and 

  push  buttons  scroll  the  display

through all the publishers on the segment showing
the  Device  Address  and  Variable  Identity  for  each
one  -  see  Fig  5.      To  aid  identification,  operating
the  P  button  will  preview  the  value  of  the  data  at
each  selected  address,  if  required  it  may  then  be
allocated  to  one  of  the  eight  BA448CF-F  listener
inputs in-1, to in-8 by operating the P button again.
If  the  format  of  the  data  at  the  selected  Device
Address and Variable Identity is not DS-65 (float +
status) ‘no dAt’ will be displayed.

Fig 5  Device Address and Variable Identity

If  the  Device  Address  and  Variable  Identity  of  the
process variable to be displayed by the BA448CF-
F  indicator  are  known,  they  may  be  directly
entered  via  the  edit  sub-menu.    This  sub-menu
also  provides  full  control  of  both  the  numeric  and
bargraph display parameters.

Summary of Contents for BA448CF-F

Page 1: ...Issue 3 23 rd June 2011 BA448CF F FOUNDATION fieldbus Intrinsically safe Panel mounting 8 variable Fieldbus Indicator Issue 3...

Page 2: ...arameters 6 3 5 Enter address display parameters 6 3 6 Enable selected input 6 3 7 Enter Device Address 6 3 8 Enter Variable Identity 6 3 9 Decimal point position 6 3 10 Configuration of bargraph 6 3...

Page 3: ...indicates the protocol but is not shown on the instrument certification label There is an alternative version of the fieldbus display order code BA448CF P for use on PROFIBUS PA networks 1 1 Documenta...

Page 4: ...perature between 40 and 70 o C Note minimum guaranteed operating temperature is 20 C 3 3 Fieldbus connection The BA448CF F Indicator is powered and communicates via the fieldbus which is connected to...

Page 5: ...O applications the BA448CF F Fieldbus Indicator has a higher voltage entity intrinsic safety input parameter allowing connection to a wide range of fieldbus segments The BA448CF F Fieldbus Indicator m...

Page 6: ...that even in the event of rare incidents an ignition source due to impact or friction between the aluminium enclosure at the rear of the instrument mounting panel and iron steel is excluded Fig 2 BA4...

Page 7: ...nditioned as a fieldbus listener see section 6 3 13 to change it to a fieldbus node 6 2 1 Reset the indicator to node factory defaults rESEt The BA448CF F may be reset to the factory defaults that are...

Page 8: ...the P button causes the BA448CF F indicator to search the fieldbus segment to which it is connected for all publishers Fig 5 shows how the indicator displays the hexadecimal Device Address and Variabl...

Page 9: ...vice Address and Variable Identity Parameters can not be changed from within this function See section 6 3 4 Edit Enter addresses and display parameters Contains six sub functions that enable known fi...

Page 10: ...10...

Page 11: ...splayed pressing E will allocate the selected process variable to the selected input and return the display to the Device Address and Variable Identity from which another process variable may be selec...

Page 12: ...function pressing P again will reveal the existing bargraph justification The or button will scroll through the four options when the required justification is displayed pressing E will enter the sele...

Page 13: ...ration menu using the or button To enter the function press P which will show that the instrument is configured as a fieldbus listener to change to a fieldbus node press the or button which will toggl...

Page 14: ...normal operation after a few seconds the model number followed by the firmware version will be displayed prior to entering the display mode 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BE...

Page 15: ...und the liquid crystal display If specified when the instrument is ordered this can be supplied printed with units of measurement and a scale for the horizontal bargraph 8 2 Tag number The BA448CF F c...

Page 16: ...BA448CF F complies with the FISCO Field Device requirements specified in IEC60079 27 The intrinsically safe system shown in Fig 1 of this manual may therefore be used for installations in the USA and...

Page 17: ...17...

Page 18: ...18...

Page 19: ...19...

Page 20: ...20...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...BA448CF F may be installed in Zone 0 explosive gas air mixture continuously present Note Special conditions for safe use apply see above Zone 1 explosive gas air mixture likely to occur in normal oper...

Reviews: