3.2  Zones, gas groups and T rating
The  BA448CF-F  has  been  issued  with  EC  Type
Examination 

certificate 

ITS06ATEX25314/2X

which  has  been  used  to  confirm  compliance  with
the  requirements  for  Group  II  Category  1G  Ga  Ex
ia  IIC  T4  (Tamb        –40  to  70

o

C)  specified  in  the

ATEX  Directive.    When  connected  to  a  suitable
certified  system  the  BA448CF-F  may  be  installed
in:

Zone 0

explosive gas air mixture
continuously present.
Note:  Special conditions for
safe use apply see section 5.1

Zone 1

explosive gas air mixture
likely to occur in normal
operation.

Zone 2

explosive  gas  air  mixture  not
likely to occur, and if it does will
only exist for a short time.

Be used with gases in groups:

Group   A    propane
Group   B    ethylene
Group   C    hydrogen

Having a temperature classification of:

T1

450oC

T2

300oC

T3

200oC

T4

135oC

At an ambient temperature between –40 and
+70

o

C.

Note: minimum guaranteed operating temperature
is –20ºC.

3.3   Fieldbus connection
The  BA448CF-F  Indicator  is  powered  and
communicates via the fieldbus, which is connected
to  terminals  1  and  2.      These  are  non-polarised,
comply with the Fieldbus Intrinsically Safe Concept
(FISCO)  defined  in  EN  60079  Part  27  and  have
separate entity parameters shown below:

                          FISCO                  Entity

Ui

=

17.5V dc

22.0V dc

Ii

=

380mA dc

250mA dc

Pi

=

5.32W

1.2W

The 

maximum 

equivalent 

capacitance 

and

inductance at terminals 1 & 2 is:

Ci

=     0

Li

=     8µH

3.4 Certification Label Information
The certification information label is fitted to the top
outer surface of the enclosure.  It shows details of
the  ATEX  certification  and  a  statement  that  the
instrument  is  a  FISCO  Field  Device,  plus  BEKA
associates  name  and  location.  IECEx  approval
information  is  also  included.    The  label  may  also
contain non-European certification information.
The  instrument  serial  number  and  year  of
manufacture are shown on the rear panel adjacent
to the terminals.

Summary of Contents for BA448CF-F

Page 1: ...Issue 3 23 rd June 2011 BA448CF F FOUNDATION fieldbus Intrinsically safe Panel mounting 8 variable Fieldbus Indicator Issue 3...

Page 2: ...arameters 6 3 5 Enter address display parameters 6 3 6 Enable selected input 6 3 7 Enter Device Address 6 3 8 Enter Variable Identity 6 3 9 Decimal point position 6 3 10 Configuration of bargraph 6 3...

Page 3: ...indicates the protocol but is not shown on the instrument certification label There is an alternative version of the fieldbus display order code BA448CF P for use on PROFIBUS PA networks 1 1 Documenta...

Page 4: ...perature between 40 and 70 o C Note minimum guaranteed operating temperature is 20 C 3 3 Fieldbus connection The BA448CF F Indicator is powered and communicates via the fieldbus which is connected to...

Page 5: ...O applications the BA448CF F Fieldbus Indicator has a higher voltage entity intrinsic safety input parameter allowing connection to a wide range of fieldbus segments The BA448CF F Fieldbus Indicator m...

Page 6: ...that even in the event of rare incidents an ignition source due to impact or friction between the aluminium enclosure at the rear of the instrument mounting panel and iron steel is excluded Fig 2 BA4...

Page 7: ...nditioned as a fieldbus listener see section 6 3 13 to change it to a fieldbus node 6 2 1 Reset the indicator to node factory defaults rESEt The BA448CF F may be reset to the factory defaults that are...

Page 8: ...the P button causes the BA448CF F indicator to search the fieldbus segment to which it is connected for all publishers Fig 5 shows how the indicator displays the hexadecimal Device Address and Variabl...

Page 9: ...vice Address and Variable Identity Parameters can not be changed from within this function See section 6 3 4 Edit Enter addresses and display parameters Contains six sub functions that enable known fi...

Page 10: ...10...

Page 11: ...splayed pressing E will allocate the selected process variable to the selected input and return the display to the Device Address and Variable Identity from which another process variable may be selec...

Page 12: ...function pressing P again will reveal the existing bargraph justification The or button will scroll through the four options when the required justification is displayed pressing E will enter the sele...

Page 13: ...ration menu using the or button To enter the function press P which will show that the instrument is configured as a fieldbus listener to change to a fieldbus node press the or button which will toggl...

Page 14: ...normal operation after a few seconds the model number followed by the firmware version will be displayed prior to entering the display mode 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BE...

Page 15: ...und the liquid crystal display If specified when the instrument is ordered this can be supplied printed with units of measurement and a scale for the horizontal bargraph 8 2 Tag number The BA448CF F c...

Page 16: ...BA448CF F complies with the FISCO Field Device requirements specified in IEC60079 27 The intrinsically safe system shown in Fig 1 of this manual may therefore be used for installations in the USA and...

Page 17: ...17...

Page 18: ...18...

Page 19: ...19...

Page 20: ...20...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...BA448CF F may be installed in Zone 0 explosive gas air mixture continuously present Note Special conditions for safe use apply see above Zone 1 explosive gas air mixture likely to occur in normal oper...

Reviews: