16

APPENDIX 1
FM Approval for use in the USA and
cFM Approval for use in Canada

A1.0  Factory Mutual Approval
For  installations  in  the  USA  and  Canada,  the
BA448CF-F  has  FM  and  cFM  intrinsic  safety  and
nonincendive 

approval, 

project 

identifications

3027031  and  3027031C.        Copies  of  the
Certificates  of  Compliance  are  available  from
BEKA associates sales office and www.beka.co.uk

A1.1  Intrinsic safety  approval
The  BA448CF-F  is  approved  to  FM  Class  3610
intrinsic  safety  standard  for  use  in  hazardous
(classified)  locations.    Installations  must  comply
with  BEKA  associates  Control  Drawing  CI410-12,
which  is  attached  to  this  Appendix,  ANSI/ISA
RP12.06.01  ‘Installation  of  Intrinsically  Safe
Systems for Hazardous (Classified) Locations’ and
with the National Electrical Code ANSI/NFPA70.

Canadian  installations  must  comply  with  the
Canadian  Electrical  Code  C22.2  and  with  BEKA
associates  Control  Drawing  CI410-12,  which  is
attached to this Appendix.

The  BA448CF-F  has  a  T4  rating  at  ambient
temperatures  up  to  +70

o

C  and  may  be  used  with

the following gases and dusts:

Intrinsic Safety

Division 1 or 2

Class I    Group A & B
               Group C
               Group D

Class II   Group E, F & G

Class  III

Zone 0, 1 or 2

Class 1   Group IIC
               Group IIB
               Group IIA

The FM and cFM entity parameters are identical to
the  ATEX  parameters  and,  like  the  ATEX
certification, confirm that the  BA448CF-F complies
with  the  FISCO  Field  Device  requirements
specified  in  IEC60079-27.    The  intrinsically  safe
system  shown  in  Fig  1  of  this  manual  may
therefore  be  used  for  installations  in  the  USA  and
Canada,  providing  the  fieldbus  power  supply,
terminators,  Zener  barriers  and  galvanic  isolators
are  FM  Approved  for  US  installations  and  cFM  or
CSA  Approved  for  Canadian  installations.  All
installations  must  comply  with  BEKA  associates
Control Drawing CI410-12.

FM and cFM Approvals also allows  the  BA448CF-
F  to  be  connected  to  non-FISCO  systems  using
the entity concept – see section 4.2 of this manual.

A1.2  Nonincendive approval
The  BA448CF-F  is  FM  Class  3611  nonincendive
approved  allowing  it  to  be  installed  in  Division  2
hazardous  (classified)  locations  without  the  need
for  Zener  barriers  or  galvanic  isolators.      US
installations 

must 

comply 

with 

the 

BEKA

associates  Control  Drawing  CI410-13,  which  is
attached  to  this  Appendix,  and  with  the  National
Electrical Code ANSI/NFPA70.

Canadian  nonincendive  installations  must  comply
with  the  Canadian  Electrical  Code  C22.2  and  with
BEKA associates Control Drawing CI410-13, which
is attached to this Appendix.

The  FM  and  cFM  Nonincendive  Approvals  also
allow  the  BA448CF-F  fieldbus  indicator  to  be
connected  to  any  appropriately  certified  FNICO
compliant fieldbus segment.

The  BA448CF-F  has  a  T4  rating  at  ambient
temperatures  up  to  +70ºC  and  may  be  used  with
the following gases:

Nonincendive

Division 2

Class I    Group A & B
               Group C
               Group D

Zone 2

Class I    Group IIC
               Group IIB
               Group IIA

Summary of Contents for BA448CF-F

Page 1: ...Issue 3 23 rd June 2011 BA448CF F FOUNDATION fieldbus Intrinsically safe Panel mounting 8 variable Fieldbus Indicator Issue 3...

Page 2: ...arameters 6 3 5 Enter address display parameters 6 3 6 Enable selected input 6 3 7 Enter Device Address 6 3 8 Enter Variable Identity 6 3 9 Decimal point position 6 3 10 Configuration of bargraph 6 3...

Page 3: ...indicates the protocol but is not shown on the instrument certification label There is an alternative version of the fieldbus display order code BA448CF P for use on PROFIBUS PA networks 1 1 Documenta...

Page 4: ...perature between 40 and 70 o C Note minimum guaranteed operating temperature is 20 C 3 3 Fieldbus connection The BA448CF F Indicator is powered and communicates via the fieldbus which is connected to...

Page 5: ...O applications the BA448CF F Fieldbus Indicator has a higher voltage entity intrinsic safety input parameter allowing connection to a wide range of fieldbus segments The BA448CF F Fieldbus Indicator m...

Page 6: ...that even in the event of rare incidents an ignition source due to impact or friction between the aluminium enclosure at the rear of the instrument mounting panel and iron steel is excluded Fig 2 BA4...

Page 7: ...nditioned as a fieldbus listener see section 6 3 13 to change it to a fieldbus node 6 2 1 Reset the indicator to node factory defaults rESEt The BA448CF F may be reset to the factory defaults that are...

Page 8: ...the P button causes the BA448CF F indicator to search the fieldbus segment to which it is connected for all publishers Fig 5 shows how the indicator displays the hexadecimal Device Address and Variabl...

Page 9: ...vice Address and Variable Identity Parameters can not be changed from within this function See section 6 3 4 Edit Enter addresses and display parameters Contains six sub functions that enable known fi...

Page 10: ...10...

Page 11: ...splayed pressing E will allocate the selected process variable to the selected input and return the display to the Device Address and Variable Identity from which another process variable may be selec...

Page 12: ...function pressing P again will reveal the existing bargraph justification The or button will scroll through the four options when the required justification is displayed pressing E will enter the sele...

Page 13: ...ration menu using the or button To enter the function press P which will show that the instrument is configured as a fieldbus listener to change to a fieldbus node press the or button which will toggl...

Page 14: ...normal operation after a few seconds the model number followed by the firmware version will be displayed prior to entering the display mode 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BE...

Page 15: ...und the liquid crystal display If specified when the instrument is ordered this can be supplied printed with units of measurement and a scale for the horizontal bargraph 8 2 Tag number The BA448CF F c...

Page 16: ...BA448CF F complies with the FISCO Field Device requirements specified in IEC60079 27 The intrinsically safe system shown in Fig 1 of this manual may therefore be used for installations in the USA and...

Page 17: ...17...

Page 18: ...18...

Page 19: ...19...

Page 20: ...20...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...BA448CF F may be installed in Zone 0 explosive gas air mixture continuously present Note Special conditions for safe use apply see above Zone 1 explosive gas air mixture likely to occur in normal oper...

Reviews: