6.3.7  Enter Device Address    ‘Adr’
This  function  allows  a  known  fieldbus  Device
Address  to  be  entered  and  allocated  to  the
indicator  input  selected  in  the  Edit  function.  To
enter  the  function  press  P  which  will  reveal  the
existing  two  digit  hexadecimal  address  with  one
digit  flashing  which  may  be  changed  by  operating
the 

  or 

  button.      When  set  as  required

operating  the  P  button  will  transfer  control  to  the
second  digit  that  may  be  adjusted  in  the  same
way.    When  both  digits  are  set  as  required
operating  the  E  button  will  enter  the  selection  and
return to the ‘Adr’ prompt in the edit sub-menu.

6.3.8  Enter Variable Identity    ‘id’
Enables  a  known  Variable  Identity  to  be  entered
and  allocated to the  indicator  input  selected  in  the
Edit  function.  To  enter  the  function  press  P  which
will  reveal  the  existing  two  digit  hexadecimal
address  with  one  digit  flashing  which  may  be
changed  by  operating  the 

  or 

  button.  When

set as required operating the P  button  will transfer
control to the second digit that may be adjusted in
the  same  way.    When  both  digits  are  set  as
required  operating  the  E  button  will  enter  the
selection  and  return  to  the  ‘id’  prompt  in  the  edit
sub-menu.

6.3.9  Decimal point position    ‘dP’
Defines  the  position  the  decimal  point  in  the
numeric  display.    To  enter  the  function  press  P
which  will  reveal  the  existing  decimal  point
position.    Operating  the 

  or 

  button  will  move

the  decimal  point  to  the  required  position,  omit  it,
or 

activate 

all 

the 

decimal 

points 

which

automatically  provides    maximum  resolution  in  the
display mode irrespective of the numeric value.
When  positioned  as  required,  operating  the  E
button will enter the selection and return to the ‘dP’
prompt in the edit sub-menu.

6.3.10  Configuration of bargraph display
‘bAr’
This  function  contains  three  sub-functions  that
enable  the  bargraph,  justify  its  position  and  define
the  relationship  between  the  bargraph  and  the
instrument’s numeric display.

Sub-function  ‘b.tYPE’  allows  the  bargraph  to  be
left,  centre  or  right  justified,  or  to  be  turned  off.
Sub-functions  ‘bArLo’  and  ‘bArhi’  define  the
listener’s  numeric  display  at  which  the  bargraph
starts and is at full scale.

The ‘bAr’ function may be selected from within the
edit  sub-menu  by  operating  the 

  or 

  button.

To enter the function press P which will display the
‘b.tYPE’  sub-function,  pressing  P  again  will  reveal
the existing bargraph justification.

The 

  or 

  button  will  scroll  through  the  four

options, 

when 

the 

required 

justification 

is

displayed,  pressing  E  will  enter  the  selection  and
return the display to the ‘b.tYPE’ prompt in the edit
sub-menu  from  which  ‘bArLo’  may  be  selected
using the 

 or 

 button.

‘bArLo’  defines  the  indicator’s  numeric  display  at
which  the  bargraph  starts,  to  enter  the  function
press P which will reveal the existing setting.   The
display may  be changed using the 

  or 

  button

to  adjust  the  flashing  digit  and  the  P  button  to
move control to  the  next  digit.   When  the  required
starting  display  has  been  selected,  press  E  to
return  to  the  ‘bArLo’  prompt  in  the  edit  sub-menu
from which the ‘bArHi’ function may be selected.

‘bArHi’  defines  the  indicator’s  numeric  display  at
which  the  bargraph  is  full  scale,  to  enter  the
function  press  P  which  will  reveal  the  existing
setting.   The display may be changed using the 

or 

  button  to  adjust  the  flashing  digit  and  the  P

button to move control to the next digit.  When the
required  display  has  been  selected,  press  E  twice
to  enter  the  new  values  and  return  to  the  ‘bAr’
prompt in the edit sub-menu.

Note:  If  the  ‘dP’  function  has  been  set  to  provide
automatic  maximum  resolution  irrespective  of  the
displayed  value,  it  may  be  necessary  to  manually
position  the  decimal  point  before  adjusting  ‘bArLo’
or  ‘bArHi’.      This  can  be  achieved  by  repeatedly
operating  the  P  button  until  the  activated  decimal
point  flashes,  the  decimal  point  can  then  be
positioned  using  either  the 

  or 

  button.

Pressing  the  P  button  again  will  return  control  to
one of the digits.

6.3.11  Scale numeric display    ‘SCALE’
A  scaling  factor  ‘Gain’  and  an  offset  ‘oFFSt’  may
be  applied  to  the  fieldbus  process  variable  using
this  function,  thus  allowing  the  indicator  to  display
the fieldbus process variable in alternative units.

The ‘SCALE’ function may be selected from within
the edit sub-menu by operating the 

 or 

 button.

To enter the function press P which will display the
‘GAin’  sub-function,  pressing  P  again  will  reveal
the  existing  gain  with  one  digit  flashing.  This
flashing  digit may  be  changed  by  operating  the 

or 

▲ button; when adjusted the 

P button will move

control  to  the  next  digit  or  to  the  decimal  point
which can be positioned using the 

 or 

 button.

When  ‘GAin’  has  been  set  to  the  required  value
operating  the  E  button  will  enter  the  selection  and
return  to  the  ‘GAin’  prompt  in  the  sub-menu  from
where  the  ‘oFFSt’  function  can  be  selected  using
the 

 or 

 button.

Summary of Contents for BA448CF-F

Page 1: ...Issue 3 23 rd June 2011 BA448CF F FOUNDATION fieldbus Intrinsically safe Panel mounting 8 variable Fieldbus Indicator Issue 3...

Page 2: ...arameters 6 3 5 Enter address display parameters 6 3 6 Enable selected input 6 3 7 Enter Device Address 6 3 8 Enter Variable Identity 6 3 9 Decimal point position 6 3 10 Configuration of bargraph 6 3...

Page 3: ...indicates the protocol but is not shown on the instrument certification label There is an alternative version of the fieldbus display order code BA448CF P for use on PROFIBUS PA networks 1 1 Documenta...

Page 4: ...perature between 40 and 70 o C Note minimum guaranteed operating temperature is 20 C 3 3 Fieldbus connection The BA448CF F Indicator is powered and communicates via the fieldbus which is connected to...

Page 5: ...O applications the BA448CF F Fieldbus Indicator has a higher voltage entity intrinsic safety input parameter allowing connection to a wide range of fieldbus segments The BA448CF F Fieldbus Indicator m...

Page 6: ...that even in the event of rare incidents an ignition source due to impact or friction between the aluminium enclosure at the rear of the instrument mounting panel and iron steel is excluded Fig 2 BA4...

Page 7: ...nditioned as a fieldbus listener see section 6 3 13 to change it to a fieldbus node 6 2 1 Reset the indicator to node factory defaults rESEt The BA448CF F may be reset to the factory defaults that are...

Page 8: ...the P button causes the BA448CF F indicator to search the fieldbus segment to which it is connected for all publishers Fig 5 shows how the indicator displays the hexadecimal Device Address and Variabl...

Page 9: ...vice Address and Variable Identity Parameters can not be changed from within this function See section 6 3 4 Edit Enter addresses and display parameters Contains six sub functions that enable known fi...

Page 10: ...10...

Page 11: ...splayed pressing E will allocate the selected process variable to the selected input and return the display to the Device Address and Variable Identity from which another process variable may be selec...

Page 12: ...function pressing P again will reveal the existing bargraph justification The or button will scroll through the four options when the required justification is displayed pressing E will enter the sele...

Page 13: ...ration menu using the or button To enter the function press P which will show that the instrument is configured as a fieldbus listener to change to a fieldbus node press the or button which will toggl...

Page 14: ...normal operation after a few seconds the model number followed by the firmware version will be displayed prior to entering the display mode 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BE...

Page 15: ...und the liquid crystal display If specified when the instrument is ordered this can be supplied printed with units of measurement and a scale for the horizontal bargraph 8 2 Tag number The BA448CF F c...

Page 16: ...BA448CF F complies with the FISCO Field Device requirements specified in IEC60079 27 The intrinsically safe system shown in Fig 1 of this manual may therefore be used for installations in the USA and...

Page 17: ...17...

Page 18: ...18...

Page 19: ...19...

Page 20: ...20...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...BA448CF F may be installed in Zone 0 explosive gas air mixture continuously present Note Special conditions for safe use apply see above Zone 1 explosive gas air mixture likely to occur in normal oper...

Reviews: