1.  DESCRIPTION
The BA448CF-F fieldbus indicator is an intrinsically
safe FOUNDATION™ fieldbus instrument that may
be  configured  as  a  fieldbus  node  or  as  a  fieldbus
listener.  It can display up to eight fieldbus process
variables  on  a  five  digit  LCD  and  31  segment
analogue  bargraph.      The  instrument  is  bus
powered so no additional power supply is required.

As  a  fieldbus  node  the  indicator  is  configured  via
the fieldbus host.

             Communication             Fieldbus Function
                 Protocol                             Blocks

FOUNDATION™ fieldbus 

Input Selector (2 x IS)

                                  

Digital input     (6 x DI)

Device  Description  files  may  be  downloaded  from
the  Fieldbus  Foundation  or  from  the  BEKA
associates websites.

When  configured  as  a  fieldbus  listener  the
BA448CF-F  is  not  visible  to  the  fieldbus  host  and
can  only  be  configured  using  the  push  buttons  on
the front of the instrument.

Housed  in  a  robust  72  x  144  panel  mounting  DIN
enclosure,  the  BA448CF-F  fieldbus  indicator  has
an IP66 front panel and is supplied with a gasket to
seal  the  joint  between  the  instrument  and  the
panel.

The  instrument  is  intrinsically  safe  and  has  been
certified  by  European  Notified  Body  Intertek
Testing  and  Certification  Ltd  (ITS)  to  harmonised
ATEX  explosive  gas  standards,  which  has  been
used  to  confirm  compliance  with  European  ATEX
Directive 94/9/EC.

The  BA448CF-F  also  has  intrinsic  safety  and
nonincendive  FM  and  cFM  Approval  allowing
installation  in  the  USA  and  Canada  –  see
Appendix 1.

For  international  applications  the  BA448CF-F
fieldbus  indicator  has  IECEx  intrinsic  safety
approval  –  see Appendix 2.

The instrument’s communication protocol is shown
on the rear  of the instrument.  The ‘-F’ order code
suffix  also  indicates  the  protocol  but  is  not  shown
on the instrument certification label.     There is an
alternative  version  of  the  fieldbus  display,  order
code  BA448CF-P  for  use  on  PROFIBUS  PA
networks.

1.1  Documentation
This  instruction  manual  describes  ATEX  system
design  and  installation  of  the  BA448CF-F  fieldbus
indicator.System  design  information  for  non-ATEX
approvals is shown in appendices to this manual.

2.  OPERATION
The  BA448CF-F  fieldbus  indicator  can  display  up
to  eight  pre-configured  FOUNDATION™  fieldbus
process  variables  designated  in-1  to  in-8.      The
operator  can  select  which  variable  is  displayed
using  the 

and 

  push  buttons  which  scroll  the

display  through  the  eight  inputs.      A  numeric
annunciator  on  the  left  hand  side  of  the  display
shows  which  of  the  eight  inputs  is  currently  being
displayed.

2.1  Error messages
When  the  BA448CF-F  is  configured  as  a  listener
the following error messages may be displayed:

‘no ConF’

No inputs have been
configured or are enabled.

‘no dAtA’

No data is being received
with the current configuration.

3.  INTRINSIC SAFETY CERTIFICATION

3.1 ATEX certificate
The BA448CF-F has been issued with an EC-Type
Examination  Certificate  by  Notified  Body  Intertek
Testing  and  Certification  Ltd  (ITS)  that  has  been
used  to  confirm  compliance  with  the  European
ATEX Directive 94/9/EC for Group II, Category 1G,
gas atmospheres, Ga Ex ia IIC T4.  The instrument
bears  the  Community  Mark  and,  subject  to  local
codes  of  practice,  may  be  installed  in  any  of  the
European 

Economic 

Area 

(EEA) 

member

countries.    ATEX  certificates  are  also  acceptable
for installations in Switzerland.

This  manual  describes  ATEX  installations  in
explosive  gas  atmospheres  that  conform  with
EN 

60079:Part14 

Electrical 

Installation 

in

Hazardous  Areas.    When  designing  systems  for
installation  outside  the  UK,  the  local  Code  of
Practice should be consulted.

Summary of Contents for BA448CF-F

Page 1: ...Issue 3 23 rd June 2011 BA448CF F FOUNDATION fieldbus Intrinsically safe Panel mounting 8 variable Fieldbus Indicator Issue 3...

Page 2: ...arameters 6 3 5 Enter address display parameters 6 3 6 Enable selected input 6 3 7 Enter Device Address 6 3 8 Enter Variable Identity 6 3 9 Decimal point position 6 3 10 Configuration of bargraph 6 3...

Page 3: ...indicates the protocol but is not shown on the instrument certification label There is an alternative version of the fieldbus display order code BA448CF P for use on PROFIBUS PA networks 1 1 Documenta...

Page 4: ...perature between 40 and 70 o C Note minimum guaranteed operating temperature is 20 C 3 3 Fieldbus connection The BA448CF F Indicator is powered and communicates via the fieldbus which is connected to...

Page 5: ...O applications the BA448CF F Fieldbus Indicator has a higher voltage entity intrinsic safety input parameter allowing connection to a wide range of fieldbus segments The BA448CF F Fieldbus Indicator m...

Page 6: ...that even in the event of rare incidents an ignition source due to impact or friction between the aluminium enclosure at the rear of the instrument mounting panel and iron steel is excluded Fig 2 BA4...

Page 7: ...nditioned as a fieldbus listener see section 6 3 13 to change it to a fieldbus node 6 2 1 Reset the indicator to node factory defaults rESEt The BA448CF F may be reset to the factory defaults that are...

Page 8: ...the P button causes the BA448CF F indicator to search the fieldbus segment to which it is connected for all publishers Fig 5 shows how the indicator displays the hexadecimal Device Address and Variabl...

Page 9: ...vice Address and Variable Identity Parameters can not be changed from within this function See section 6 3 4 Edit Enter addresses and display parameters Contains six sub functions that enable known fi...

Page 10: ...10...

Page 11: ...splayed pressing E will allocate the selected process variable to the selected input and return the display to the Device Address and Variable Identity from which another process variable may be selec...

Page 12: ...function pressing P again will reveal the existing bargraph justification The or button will scroll through the four options when the required justification is displayed pressing E will enter the sele...

Page 13: ...ration menu using the or button To enter the function press P which will show that the instrument is configured as a fieldbus listener to change to a fieldbus node press the or button which will toggl...

Page 14: ...normal operation after a few seconds the model number followed by the firmware version will be displayed prior to entering the display mode 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BE...

Page 15: ...und the liquid crystal display If specified when the instrument is ordered this can be supplied printed with units of measurement and a scale for the horizontal bargraph 8 2 Tag number The BA448CF F c...

Page 16: ...BA448CF F complies with the FISCO Field Device requirements specified in IEC60079 27 The intrinsically safe system shown in Fig 1 of this manual may therefore be used for installations in the USA and...

Page 17: ...17...

Page 18: ...18...

Page 19: ...19...

Page 20: ...20...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...BA448CF F may be installed in Zone 0 explosive gas air mixture continuously present Note Special conditions for safe use apply see above Zone 1 explosive gas air mixture likely to occur in normal oper...

Reviews: