background image

6

4.2

Remote indication

The BA304NG and the BA324NG may be driven
directly from a safe area instrument with a 4/20mA
output to provide a remote display within a Zone 2
hazardous area.   

There are four design requirements:

1. The current flowing in the 4/20mA loop, must

not exceed 100mA in normal operation.

2.

Wiring  must  comply  with  Clause  9  of
EN60079-14

 

Electrical  installation  in

hazardous areas

.

3. The instrument enclosure must be fitted with

Ex n or Ex e certified glands, conduit fittings
or blanking plugs.  

4. The safe area 4/20mA output from the safe

area instrument must be able to supply the
1.2V required to operate the indicator.   This
increases to 5.0V if the indicator includes an
optional loop powered backlight.  See 9.4.1

Fig 3 shows a typical application.

Fig 3  Remote indication in Zone 2 hazardous area

To  strictly  comply  with  the  requirements  of
EN  60079:14

  Electrical  Installation  in  Hazardous

Areas

, each of the wires entering the hazardous

area  should  be  individually  fused  and  contain  a
means  of  isolation.    However,  in  practice
instrumentation  energised  by  a  current  limited
power supply or instrument that can be switched
off is often considered adequate.

5.

INSTALLATION

5.1

Location

The  BA304NG  and  BA324NG  indicators  are
housed in robust IP66 glass reinforced polyester
(GRP) enclosures incorporating an armoured glass
window  and  stainless  steel  fittings  making  them
suitable  for  exterior  mounting  in  most  industrial
on-shore and off-shore Zone 2 installations.  The
indicators should be positioned where the display
is not in continuous direct sunlight.  

Field wiring terminals are located on the rear of the
indicator assembly as shown in Fig 5.   If the field
wiring is to be terminated prior to the installation of
the  indicator  assembly,  a  back-box  terminal
assembly,  which  includes  a  4/20mA  continuity
diode  and  additional  terminals  for  linking  cable
screens is available as an option.  See section 9.5
of this manual.

Indicator terminals 2 and 4 are internally joined and
may be used for linking the return 4/20mA wire -
see Fig 2.

The  instrument  back-box  is  supplied  with  a
bonding plate that may be mounted on the inside
or  outside  of  the  enclosure  to  ensure  electrical
continuity between the two conduit or cable entries.
The  bonding  plate  includes  an  M4  earth  stud
which, if the enclosure is not bolted to an earthed
post or structure, should be connected to the plant
potential equalising conductor.

An  insulated  M4  stud  is  provided  in  the  bottom
right hand corner the back-box for interconnecting
cable screens.

Both indicators are surface mounting, but may be
pipe  mounted  using  one  of  the  accessory  kit
described in section 9.4 of this manual.

5.2

Installation Procedure

Fig  4  illustrates  the  instrument  installation
procedure.

A. Remove  the  indicator  assembly  by

unscrewing the four captive 'A' screws.

B. Mount  the  enclosure  back-box  on  a  flat

surface  and  secure  with  screws  or  bolts
through the four 'B' holes.  Alternatively use
one  of  the  pipe  mounting  kits  described  in
section 9.4.

C. Remove the temporary hole plug and install

an  appropriate  IP  and  temperature  rated
cable gland or conduit fitting.   If two entries
are required,  the IP66 stopping plug should
be  replaced  with  an  appropriate  IP  and
temperature  rated  cable  gland  or  conduit
fitting.

D. Connect the field  wiring to the terminals as

shown  in  Fig  5.  Replace  the  instrument
assembly on the back-box and evenly tighten
the four 'A' screws.

Summary of Contents for BA304NG

Page 1: ...Issue 4 1st November 2017 BA304NG BA324NG Ex nA Ex tc loop powered field mounting indicators Issue 4...

Page 2: ...tor 7 3 Under and over range 7 4 Lineariser default configuration 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine maintenance 8 5 G...

Page 3: ...Notified Body Intertek Testing and Certification Ltd which has been used to confirm compliance with the European ATEX Directive 2014 34 EU For international applications both models have IECEx certifi...

Page 4: ...and dust certification This section of the instruction manual describes ATEX gas certification ATEX dust certification is described in Appendix 1 and IECEx approvals are described in Appendix 2 3 1 A...

Page 5: ...to display the measured variable or control signal in engineering units The indicators are transparent to HART signals There are four design requirements 1 The current flowing in the 4 20mA loop must...

Page 6: ...on the rear of the indicator assembly as shown in Fig 5 If the field wiring is to be terminated prior to the installation of the indicator assembly a back box terminal assembly which includes a 4 20m...

Page 7: ...ors are supplied with a printed scale card showing the requested units of measurement and tag information If this information is not supplied when the indicator is ordered a blank scale card will be f...

Page 8: ...r this prompt allowing each digit of the code to be entered using the and push buttons and the button to move control to the next digit When the correct four digit code has been entered pressing will...

Page 9: ...djusted without the need for an accurate input current or disconnection from the 4 20mA loop See section 6 6 bAr Bargraph format and calibration Only the BA324NG has a bargraph The bargraph may be con...

Page 10: ...10...

Page 11: ...not required it should be positioned beyond the most or least significant digit When positioned as required press the button to enter the selection and return to the configuration menu 6 5 Calibration...

Page 12: ...cator s digital display at which the bargraph starts is defined by the bArLo sub function which is selected by pressing the button followed by the button which will reveal the current indicator displa...

Page 13: ...ions shown in sections 6 0 and 7 3 To reset the indicator or lineariser select r5Et from the configuration menu and press the indicator will display one of the reset options ConF or LtAb ConF Resets t...

Page 14: ...ows direct calibration of the lineariser with an external current source and is the preferred method when traceability is required If the exact system non linearity is unknown this method also allows...

Page 15: ...15...

Page 16: ...ng break point 7 1 1 Example Adding break points to a new indicator When adding break points to a new indicator or to a lineariser following resetting to the factory defaults using the LtAb function d...

Page 17: ...n by pressing the button The corresponding indicator display at each of the break points can now be defined using the di5P sub function Using the and buttons select the di5P sub function and press whi...

Page 18: ...o risk of a flammable atmospjher being present If an indicator fails after it has been functioning correctly follow the procedure shown in section 8 1 If this does not reveal the cause of the fault it...

Page 19: ...haracters 5mm high 9 2 Display backlight The BA304NG and BA324NG loop powered indicators can be supplied with a factory fitted backlight that may be loop or separately powered When loop powered the ba...

Page 20: ...s an emergency shut down system Both models can be supplied with factory fitted dual solid state single pole alarm outputs Each alarm output may be independently conditioned as a high or low alarm wit...

Page 21: ...lication in which a BA304NG or BA324NG indicator is displaying the output from a 2 wire transmitter in Zone 2 Alarm 1 is switching a solenoid valve in Zone 2 and alarm 2 is switching a sounder located...

Page 22: ...tpoint The alarm is activated when the indicator display equals the setpoint See section 9 3 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 3 6 no nC Normally open or n...

Page 23: ...23...

Page 24: ...e for fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and pr...

Page 25: ...t having access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This dir...

Page 26: ...plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 18 Fig 18 Displayed value and setpoints on bargraph T...

Page 27: ...supplied with each panel mounting kit 9 6 Back box terminal assembly If it is necessary to terminate the field wiring prior to the installation of the indicator display a back box terminal assembly is...

Page 28: ...o be used for Zone 22 combustible dust applications The indicator should be located where the minimum amount of dust will accumulate on the enclosure and the installation should be as specified in thi...

Page 29: ...USA and Canada A3 0 cETL Mark For installations in the USA and Canada the BA304NG and BA324NG indicators have ETL and cETL Ex nA and Ex tc approval Control Number 4008610 Copies of the Authorisation...

Reviews: