background image

25

9.3.10 Alarm silence time:  

5iL

This function is primarily intended for use in small
installations  where  the  alarm  output  directly
operates an alarm annunciator such as a sounder
or beacon.  When the alarm silence time, which is
adjustable  between  0  and  3600  seconds  in  1
second increments, is set to any figure other than
zero,  the  

(

  push  button  becomes  an  alarm

accept  button.      After  an  alarm  has  occurred,
operating the 

(

 button will cause the alarm output

to  revert  to  the  non-alarm  condition  for  the
programmed  alarm  silence  time.    If  the  alarm
condition still exists at the end of the silence time,
the alarm  output will  be reactivated.  During the
silence  time  the  indicator  alarm  annunciator  will
flash until the silence time expires or the alarm is
cleared.

If  the  

FL5H

  function,  which  flashes  the  indicator

display when an alarm occurs has been enabled, it
will  only  function  when  the  alarm  output  is
activated, not during the silence time.  See section
9.3.11

To adjust the alarm silence time select  

5iL

 from

the alarm configuration menu and press 

(

 which

will reveal the existing silence time.  The flashing
digit of the silence time can be adjusted using the

&

 and  

*

  push  buttons,  and  the  

(

 button  to

move  control  to  the  other  digits.    When  the
required silence time has been entered press  

)

to return to the alarm menu.

9.3.11 Flash display when alarm occurs:  

FL5H

In addition to the two alarm annunciators on the
top left hand corner of the indicator display which
show  the  status  of  both  alarms,  this  function
provides an even more conspicuous indication that
an alarm condition has occurred.

When enabled, the function alternates the indicator
display between the numerical value and the alarm
reference, 

ALr1

 or 

ALr2

, when the alarm output is

activated.  If both alarm outputs are activated, the
alarm references are displayed in sequence.

To enable or disable the function select 

FL5H

 from

the alarm menu and press 

(

 which will reveal the

current  setting  

on

 or  

oFF

.   The  function  can

changed by pressing the 

&

 or 

*

 button followed

by the 

)

 button to return to the alarm menu.

9.3.12 Access setpoint in display mode:  

AC5P

This function enables a separate menu providing
access  to  the  alarm  setpoints  from  the  display
mode by simultaneously operating the 

(

 and 

*

push buttons.  An operator can therefore adjust the
alarm  setpoints  without  having  access  to  the
indicator  configuration  menu.    Protection  against
accidental  adjustment  of  the  setpoints  when  the
indicator is in the display mode is provided by a
separate security code.

This direct setpoint access menu is enabled and
the separate security code entered from the  

AC5P

function in the alarm configuration menu as shown
in Fig 16.  To change the menu parameters select

AC5P

  from  the  configuration  menu  and  press

(

  which  will  display  the  enable  prompt  

EnbL

.

Press 

(

 again to reveal if the direct access menu

is 

on

 or 

oFF

.  The 

&

 or 

*

 button will toggle the

display between the two conditions.

If 

oFF

 is selected, the operator will not have access

to the setpoints from the display mode.  Return to
the 

AC5P

 prompt in the main menu by pressing 

)

twice.

If  

on

  is  selected,  the  operator  will  have  direct

access  to  the  alarm  setpoints  from  the  display
mode via  a separate  optional security code.  To
define  this  four  digit  security  code  press  

(

 to

return to the 

Enbl

 prompt followed by the 

&

 or 

*

button  to  select  the  access  code  prompt  

ACCd

.

Pressing  

(

 will reveal the current security code.

Each  digit  of  the  code  may  be  changed  by
operating the 

&

 and 

*

 push buttons, and the 

(

button to move control to the next digit.  When the
required code has been entered, press 

)

 twice to

return  to  the  

AC5P

  prompt  in  the  configuration

menu.

Default  code  

0000

  will  disable  the  security  code

allowing  direct  access  to  the  setpoints  in  the
display mode by pressing the  

(

 and  

*

 buttons

simultaneously.  Unless otherwise requested new
instruments  with  alarms  are  supplied  with  this
function disabled and the security code set to 

0000

.

9.3.13 Adjusting alarm setpoints from the

display mode.

Access  to  the  alarm  setpoints  from  the  indicator
display mode is obtained by operating the 

(

 and

*

 push buttons simultaneously as shown in Fig

17.  If the setpoints are not protected by a security
code  the  alarm  setpoint  prompt  

5P1

 will  be

displayed.    If  the  setpoints  are  protected  by  a
security  code,  

Code

 will  be  displayed  first.

Pressing  

(

 again will enable the alarm security

code to be entered digit by digit using the 

&

 and

*

 buttons to change the flashing digit, and the 

(

push button to move control to the next digit.  If the
correct  code  is  entered  pressing  

)

 will  cause

alarm  setpoint  prompt  

5P1

 to  be  displayed.

Pressing  the  

&

 or  

*

  button  will  toggle  the

display  between  the  two  alarm  setpoint  prompts

5P1

 and 

5P2

.

If an incorrect security code is entered, or a button
is not pressed within twenty seconds, the indicator
will automatically return to the display mode.

Summary of Contents for BA304NG

Page 1: ...Issue 4 1st November 2017 BA304NG BA324NG Ex nA Ex tc loop powered field mounting indicators Issue 4...

Page 2: ...tor 7 3 Under and over range 7 4 Lineariser default configuration 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine maintenance 8 5 G...

Page 3: ...Notified Body Intertek Testing and Certification Ltd which has been used to confirm compliance with the European ATEX Directive 2014 34 EU For international applications both models have IECEx certifi...

Page 4: ...and dust certification This section of the instruction manual describes ATEX gas certification ATEX dust certification is described in Appendix 1 and IECEx approvals are described in Appendix 2 3 1 A...

Page 5: ...to display the measured variable or control signal in engineering units The indicators are transparent to HART signals There are four design requirements 1 The current flowing in the 4 20mA loop must...

Page 6: ...on the rear of the indicator assembly as shown in Fig 5 If the field wiring is to be terminated prior to the installation of the indicator assembly a back box terminal assembly which includes a 4 20m...

Page 7: ...ors are supplied with a printed scale card showing the requested units of measurement and tag information If this information is not supplied when the indicator is ordered a blank scale card will be f...

Page 8: ...r this prompt allowing each digit of the code to be entered using the and push buttons and the button to move control to the next digit When the correct four digit code has been entered pressing will...

Page 9: ...djusted without the need for an accurate input current or disconnection from the 4 20mA loop See section 6 6 bAr Bargraph format and calibration Only the BA324NG has a bargraph The bargraph may be con...

Page 10: ...10...

Page 11: ...not required it should be positioned beyond the most or least significant digit When positioned as required press the button to enter the selection and return to the configuration menu 6 5 Calibration...

Page 12: ...cator s digital display at which the bargraph starts is defined by the bArLo sub function which is selected by pressing the button followed by the button which will reveal the current indicator displa...

Page 13: ...ions shown in sections 6 0 and 7 3 To reset the indicator or lineariser select r5Et from the configuration menu and press the indicator will display one of the reset options ConF or LtAb ConF Resets t...

Page 14: ...ows direct calibration of the lineariser with an external current source and is the preferred method when traceability is required If the exact system non linearity is unknown this method also allows...

Page 15: ...15...

Page 16: ...ng break point 7 1 1 Example Adding break points to a new indicator When adding break points to a new indicator or to a lineariser following resetting to the factory defaults using the LtAb function d...

Page 17: ...n by pressing the button The corresponding indicator display at each of the break points can now be defined using the di5P sub function Using the and buttons select the di5P sub function and press whi...

Page 18: ...o risk of a flammable atmospjher being present If an indicator fails after it has been functioning correctly follow the procedure shown in section 8 1 If this does not reveal the cause of the fault it...

Page 19: ...haracters 5mm high 9 2 Display backlight The BA304NG and BA324NG loop powered indicators can be supplied with a factory fitted backlight that may be loop or separately powered When loop powered the ba...

Page 20: ...s an emergency shut down system Both models can be supplied with factory fitted dual solid state single pole alarm outputs Each alarm output may be independently conditioned as a high or low alarm wit...

Page 21: ...lication in which a BA304NG or BA324NG indicator is displaying the output from a 2 wire transmitter in Zone 2 Alarm 1 is switching a solenoid valve in Zone 2 and alarm 2 is switching a sounder located...

Page 22: ...tpoint The alarm is activated when the indicator display equals the setpoint See section 9 3 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 3 6 no nC Normally open or n...

Page 23: ...23...

Page 24: ...e for fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and pr...

Page 25: ...t having access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This dir...

Page 26: ...plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 18 Fig 18 Displayed value and setpoints on bargraph T...

Page 27: ...supplied with each panel mounting kit 9 6 Back box terminal assembly If it is necessary to terminate the field wiring prior to the installation of the indicator display a back box terminal assembly is...

Page 28: ...o be used for Zone 22 combustible dust applications The indicator should be located where the minimum amount of dust will accumulate on the enclosure and the installation should be as specified in thi...

Page 29: ...USA and Canada A3 0 cETL Mark For installations in the USA and Canada the BA304NG and BA324NG indicators have ETL and cETL Ex nA and Ex tc approval Control Number 4008610 Copies of the Authorisation...

Reviews: