background image

17

To add a break-point using the  

&

 or  

*

 button

select 

5Et

 from the configuration menu and press

(

 which will result in the 

Add

 sub-function prompt

being displayed.  To enter the sub-function press

(

 which  will  reveal  the current break-point and

the  total  number  of  break-points  which  have
already been entered.  When adding a break-point
the insertion position can be selected using the 

&

and  

*

 push buttons followed by  

(

 push button

to  insert the additional break-point.  In previously
uncalibrated  linearisers  each  new  break-point
should  be  added  in  front  of  the  highest  existing
break-point, if this sequence is not followed a 

FaiL

message  will  occur  when  the  breakpoints  are
calibrated.  See example in section 7.2.1.

The delete break-point, sub-function  

dEL

 operates

in exactly the same way as the  

Add

 sub-function

described  above.    Once  within  the  

dEL

 function

each time the 

(

 button is pressed a break-point is

removed.  When  deleting  a  break-point  from  a
calibrated indicator, the break-point to be deleted
can  be  selected  using  the  

&

 and  

*

 push

buttons.  The minimum number of break-point is 2,
break-points 

0

 

:1

 and 

1

 

:1

.

When  the  required  number  of  linearising  break-
point has been entered, return to the linearisation
sub-menu  by  pressing  

)

.    The  indicator  will

display the 

Add

 or 

dEL

 prompt depending upon the

last sub-function used.  The indicator input current
and corresponding indicator display at each break-
point,  which  is  the  segment  finishing  point  as
shown in Fig 9, can now be entered using the  

in

and 

di5P

 sub-functions.

Using the 

&

 or 

*

 button select 

in

 from the sub-

menu and press  

(

 which will reveal the starting

point for the first segment 

0

 

:

 

n

, where n is the total

number of break-point entered. Press 

(

 and use

the 

&

 and 

*

 buttons and the 

(

 button to move

between  digits,  to  enter  the  input  current  in
milliamps at which the first break-point is required,
usually 4.000mA.  When set as required, press 

)

to return to the  

0

 

:

 

n

 prompt from which the next

break-point can be selected using the 

&

 and 

*

buttons.  When the required break-point has been
selected  press  

(

  and  enter  the  indicator  input

current at which this break-point is required using
the 

&

 and 

*

 buttons and the 

(

 button to move

between  digits.  Repeat  this  procedure  until  the
indicator input current at all the break-points has
been defined and then return to the 

in

 sub-function

by pressing the 

)

 button. 

The corresponding indicator display at each of the
break-points can now be defined using the  

di5P

sub-function.  Using the 

&

 and 

*

 buttons select

the  

di5P

  sub-function  and  press  

(

 which  will

reveal the starting point for the first break-point 

0

 

:

 

n

,

where  

n

  is  the  total  number  of  break-points

entered.

Press 

(

 and use the 

&

 and 

*

 buttons and the

(

  button  to  move  between  digits,  to  enter  the

required indicator display at the  first break-point.
When set as required, press 

)

 to return to the 

0

 

:

 

n

prompt  from  which  the  next  break-point  can  be
selected using the  

&

 or  

*

  buttons.   When the

required  break-point  has  been  selected  press

(

 and set the required indicator display at this

break-point.

Repeat this procedure until the indicator display at
all  the  break-points  has  been  defined  and  then
return to the 

5Et

 function in the configuration menu

by pressing the 

)

 button twice.

Error message

If during calibration the indicator displays

FAiL

 error message the current at which

the selected break-point is being set is not
above the proceeding break-point or is not
below the following break-point.

7.2.1

Example
Adding break-points to a new indicator

When adding break-points to a new indicator, or to
a  lineariser  following  resetting  to  the  factory
defaults  using  the  

LtAb

  function  described  in

section 6.11, each additional break-point should be
added  before  the  highest  existing  breakpoint.
The  first  additional  break-point  should  be  added
before the default break-point  

1

 

:1

 which will result

in a display of  

1

 

:

 

2

.  If more new break-points are

required,  using  the  

*

  button  select  the  new

highest  break-point  

2

 

:

 

2

  and  add  the  second

additional  break-point  by  operating  the  

(

 push

button which will result in a display of 

2

 

:

 

3

.  Repeat

the sequence until the required number of break-
points has been entered.

7.3

Under and over-range

The  lineariser  does  not  change  the  under  and
over-range indication described in section 6.12.  At
input  currents  below  that  specified  for  the  first
break-point  

0

 

:

 

n

, the indicator will continue to use

the specified slope of the first segment.

At input currents above that specified for the last
break-point  

n

 

:

 

n

, the indicator will continue to use

the slope specified for the last lineariser segment.

7.4

Lineariser default configuration

When the lineariser is reset to the factory defaults
using the  

LtAb

 function described in section 6.11,

the defaults conditions are:

Indicator display

BA304NG BA324NG

First break-point

0

 

:1

4mA

0.0

0.00

Second break-point

1

 

:1

20mA 100.0

100.00

Summary of Contents for BA304NG

Page 1: ...Issue 4 1st November 2017 BA304NG BA324NG Ex nA Ex tc loop powered field mounting indicators Issue 4...

Page 2: ...tor 7 3 Under and over range 7 4 Lineariser default configuration 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine maintenance 8 5 G...

Page 3: ...Notified Body Intertek Testing and Certification Ltd which has been used to confirm compliance with the European ATEX Directive 2014 34 EU For international applications both models have IECEx certifi...

Page 4: ...and dust certification This section of the instruction manual describes ATEX gas certification ATEX dust certification is described in Appendix 1 and IECEx approvals are described in Appendix 2 3 1 A...

Page 5: ...to display the measured variable or control signal in engineering units The indicators are transparent to HART signals There are four design requirements 1 The current flowing in the 4 20mA loop must...

Page 6: ...on the rear of the indicator assembly as shown in Fig 5 If the field wiring is to be terminated prior to the installation of the indicator assembly a back box terminal assembly which includes a 4 20m...

Page 7: ...ors are supplied with a printed scale card showing the requested units of measurement and tag information If this information is not supplied when the indicator is ordered a blank scale card will be f...

Page 8: ...r this prompt allowing each digit of the code to be entered using the and push buttons and the button to move control to the next digit When the correct four digit code has been entered pressing will...

Page 9: ...djusted without the need for an accurate input current or disconnection from the 4 20mA loop See section 6 6 bAr Bargraph format and calibration Only the BA324NG has a bargraph The bargraph may be con...

Page 10: ...10...

Page 11: ...not required it should be positioned beyond the most or least significant digit When positioned as required press the button to enter the selection and return to the configuration menu 6 5 Calibration...

Page 12: ...cator s digital display at which the bargraph starts is defined by the bArLo sub function which is selected by pressing the button followed by the button which will reveal the current indicator displa...

Page 13: ...ions shown in sections 6 0 and 7 3 To reset the indicator or lineariser select r5Et from the configuration menu and press the indicator will display one of the reset options ConF or LtAb ConF Resets t...

Page 14: ...ows direct calibration of the lineariser with an external current source and is the preferred method when traceability is required If the exact system non linearity is unknown this method also allows...

Page 15: ...15...

Page 16: ...ng break point 7 1 1 Example Adding break points to a new indicator When adding break points to a new indicator or to a lineariser following resetting to the factory defaults using the LtAb function d...

Page 17: ...n by pressing the button The corresponding indicator display at each of the break points can now be defined using the di5P sub function Using the and buttons select the di5P sub function and press whi...

Page 18: ...o risk of a flammable atmospjher being present If an indicator fails after it has been functioning correctly follow the procedure shown in section 8 1 If this does not reveal the cause of the fault it...

Page 19: ...haracters 5mm high 9 2 Display backlight The BA304NG and BA324NG loop powered indicators can be supplied with a factory fitted backlight that may be loop or separately powered When loop powered the ba...

Page 20: ...s an emergency shut down system Both models can be supplied with factory fitted dual solid state single pole alarm outputs Each alarm output may be independently conditioned as a high or low alarm wit...

Page 21: ...lication in which a BA304NG or BA324NG indicator is displaying the output from a 2 wire transmitter in Zone 2 Alarm 1 is switching a solenoid valve in Zone 2 and alarm 2 is switching a sounder located...

Page 22: ...tpoint The alarm is activated when the indicator display equals the setpoint See section 9 3 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 3 6 no nC Normally open or n...

Page 23: ...23...

Page 24: ...e for fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and pr...

Page 25: ...t having access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This dir...

Page 26: ...plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 18 Fig 18 Displayed value and setpoints on bargraph T...

Page 27: ...supplied with each panel mounting kit 9 6 Back box terminal assembly If it is necessary to terminate the field wiring prior to the installation of the indicator display a back box terminal assembly is...

Page 28: ...o be used for Zone 22 combustible dust applications The indicator should be located where the minimum amount of dust will accumulate on the enclosure and the installation should be as specified in thi...

Page 29: ...USA and Canada A3 0 cETL Mark For installations in the USA and Canada the BA304NG and BA324NG indicators have ETL and cETL Ex nA and Ex tc approval Control Number 4008610 Copies of the Authorisation...

Reviews: