background image

24

9.3.4

Alarm enable:  

EnbL

This function allows each alarm to be enabled or
disabled  without  altering  any  of  the  alarm
parameters.  To enable or disable the alarm select

EnbL

 from the alarm menu and press 

(

 which will

reveal the current setting 

on

 or 

oFF

.  The function

can be changed by pressing the  

&

 or 

*

 button

followed by the  

)

 button to return to the alarm

menu.

9.3.5

Setpoint adjustment:  

5P1

 and 

5P2

The  setpoint  of  each  alarm  may  be  positioned
anywhere in the numerical display of the indicator
providing that this corresponds to an input current
between 3.8 and 20.2mA. e.g. If the indicator has
been calibrated  to display 0 with 4mA input and
10000  with  20mA input,  the  two  alarm  setpoints
may  be  positioned  anywhere  between  -125  and
10125.
To adjust the setpoint select  

5P1

 or  

5P2

 from the

alarm configuration menu and press 

(

 which will

reveal  the  existing  alarm  setpoint.    The  flashing
digit of the setpoint can be adjusted using the  

&

and  

*

 push-buttons, and the  

(

 button to move

control  to  the  next  digit.    When  the  required
setpoint has been entered press  

)

 to return to

the alarm configuration menu.
The alarm setpoints may also be adjusted when
the indicator is in the display mode, see section
9.3.12.

9.3.6

Alarm function:  

Hi

 

.

 

Lo

Each alarm can be independently conditioned as a
high alarm or as a low alarm.   To check or change
the  alarm  function  select  

Hi

 

.

 

Lo

 from  the  alarm

menu and press  

(

 to reveal the current setting.

The function can be changed by pressing the  

&

or 

*

 button followed by the 

)

 button to return to

the alarm menu.

9.3.7

Alarm output status:  

no

 

.

 

nC

Configures the solid state alarm output to be open
‘no’ or to be closed 

nC

 in the non-alarm condition.

When deciding which is required, care should be
taken to ensure that the alarm output is fail safe as
illustrated in Fig 13.

no

Alarm output open in non-alarm condition

nC

Alarm output closed in non-alarm condition

CAUTION

When the 4/20mA supply is removed from
the  loop  powered  indicator,  both  alarm
outputs  will  open  irrespective  of
conditioning.    Therefore  for  fail  safe
operation  both  alarm  outputs  should  be
conditioned  to  be  open  in  the  alarm
condition 

nC

.

To check or change the alarm output status, select

no

 

.

 

nC

 from the alarm configuration menu and press

(

  to  reveal  the  setting.    The  function  may  be

changed by pressing the 

&

 or 

*

 button followed

by  the  

)

  button  to  return  to  the  alarm

configuration menu.

9.3.8

Hysteresis:  

H5tr

Hysteresis is shown in the units that the indicator
has been calibrated to display.
To adjust the hysteresis select 

H5tr

 from the alarm

menu and press  

(

  which will reveal the existing

figure.  The flashing  digit can be adjusted using
the  

&

 and  

*

 push-buttons, and the  

(

 button

will  move  control  to  the  next  digit.    When  the
required hystersis has been entered press  

)

 to

return to the alarm configuration menu.

e.g.  An indicator calibrated to display 0 to 10000,
with a high alarm set at 9000 and hysteresis of 200
will perform as follows:

The high alarm will be activated when increasing
indicator  display  equals  9000,  but  will  not  reset
until the indicator display falls below 8800.

9.3.9

Alarm delay:  

dELA

This function delays activation of the alarm output
for an adjustable time following the alarm condition
occurring.    The  delay  can  be  set  in  1  second
increments   between   0   and   3600   seconds.     If   a
delay is not required zero should be entered.  To
adjust  the  delay  select  

dELA

  from  the  alarm

configuration menu and press 

(

 which will reveal

the existing delay.  The flashing digit of the delay
can  be  adjusted  using  the  

&

 and  

*

 push

buttons, and the 

(

 button to move control to the

other digits.  When the required delay has been
entered press 

)

 to return to the alarm menu.

e.g.  An indicator with a high alarm set at 9000 and
an  alarm  delay  of  30  seconds  will  perform  as
follows:

The alarm annunciator will start to flash when an
increasing  indicator display  equals 9000, but the
alarm output will not be activated until the alarm
condition has existed continuously for 30 seconds.
When  the  alarm  output  is  activated,  the  alarm
annunciator will stop flashing and be permanently
activated.

If  the  

FL5H

  function,  which  flashes  the  indicator

display when an alarm occurs, has been enabled,
it will not start to function until the alarm output is
activated.  
See section 9.3.11

Summary of Contents for BA304NG

Page 1: ...Issue 4 1st November 2017 BA304NG BA324NG Ex nA Ex tc loop powered field mounting indicators Issue 4...

Page 2: ...tor 7 3 Under and over range 7 4 Lineariser default configuration 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine maintenance 8 5 G...

Page 3: ...Notified Body Intertek Testing and Certification Ltd which has been used to confirm compliance with the European ATEX Directive 2014 34 EU For international applications both models have IECEx certifi...

Page 4: ...and dust certification This section of the instruction manual describes ATEX gas certification ATEX dust certification is described in Appendix 1 and IECEx approvals are described in Appendix 2 3 1 A...

Page 5: ...to display the measured variable or control signal in engineering units The indicators are transparent to HART signals There are four design requirements 1 The current flowing in the 4 20mA loop must...

Page 6: ...on the rear of the indicator assembly as shown in Fig 5 If the field wiring is to be terminated prior to the installation of the indicator assembly a back box terminal assembly which includes a 4 20m...

Page 7: ...ors are supplied with a printed scale card showing the requested units of measurement and tag information If this information is not supplied when the indicator is ordered a blank scale card will be f...

Page 8: ...r this prompt allowing each digit of the code to be entered using the and push buttons and the button to move control to the next digit When the correct four digit code has been entered pressing will...

Page 9: ...djusted without the need for an accurate input current or disconnection from the 4 20mA loop See section 6 6 bAr Bargraph format and calibration Only the BA324NG has a bargraph The bargraph may be con...

Page 10: ...10...

Page 11: ...not required it should be positioned beyond the most or least significant digit When positioned as required press the button to enter the selection and return to the configuration menu 6 5 Calibration...

Page 12: ...cator s digital display at which the bargraph starts is defined by the bArLo sub function which is selected by pressing the button followed by the button which will reveal the current indicator displa...

Page 13: ...ions shown in sections 6 0 and 7 3 To reset the indicator or lineariser select r5Et from the configuration menu and press the indicator will display one of the reset options ConF or LtAb ConF Resets t...

Page 14: ...ows direct calibration of the lineariser with an external current source and is the preferred method when traceability is required If the exact system non linearity is unknown this method also allows...

Page 15: ...15...

Page 16: ...ng break point 7 1 1 Example Adding break points to a new indicator When adding break points to a new indicator or to a lineariser following resetting to the factory defaults using the LtAb function d...

Page 17: ...n by pressing the button The corresponding indicator display at each of the break points can now be defined using the di5P sub function Using the and buttons select the di5P sub function and press whi...

Page 18: ...o risk of a flammable atmospjher being present If an indicator fails after it has been functioning correctly follow the procedure shown in section 8 1 If this does not reveal the cause of the fault it...

Page 19: ...haracters 5mm high 9 2 Display backlight The BA304NG and BA324NG loop powered indicators can be supplied with a factory fitted backlight that may be loop or separately powered When loop powered the ba...

Page 20: ...s an emergency shut down system Both models can be supplied with factory fitted dual solid state single pole alarm outputs Each alarm output may be independently conditioned as a high or low alarm wit...

Page 21: ...lication in which a BA304NG or BA324NG indicator is displaying the output from a 2 wire transmitter in Zone 2 Alarm 1 is switching a solenoid valve in Zone 2 and alarm 2 is switching a sounder located...

Page 22: ...tpoint The alarm is activated when the indicator display equals the setpoint See section 9 3 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 3 6 no nC Normally open or n...

Page 23: ...23...

Page 24: ...e for fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and pr...

Page 25: ...t having access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This dir...

Page 26: ...plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 18 Fig 18 Displayed value and setpoints on bargraph T...

Page 27: ...supplied with each panel mounting kit 9 6 Back box terminal assembly If it is necessary to terminate the field wiring prior to the installation of the indicator display a back box terminal assembly is...

Page 28: ...o be used for Zone 22 combustible dust applications The indicator should be located where the minimum amount of dust will accumulate on the enclosure and the installation should be as specified in thi...

Page 29: ...USA and Canada A3 0 cETL Mark For installations in the USA and Canada the BA304NG and BA324NG indicators have ETL and cETL Ex nA and Ex tc approval Control Number 4008610 Copies of the Authorisation...

Reviews: