background image

27

9.4  Pipe mounting kit

The BA393G is a 316 stainless steel kit which will
fix either indicator to a horizontal or vertical pipe
with an outside diameter between 40 and 73mm.

Detailed  assembly  instructions  are  supplied  with
each BA393G pipe mounting kit.

9.5  Panel mounting kits

Two alternative panel mounting kits are available
for the BA304NG and BA324NG indicators. 

The BA394G kit consists of two 316 stainless steel
brackets  which  secure  an  indicator  into  a  panel
aperture.  The kit does not seal the joint between
the panel and the instrument and it is intended for
mounting an indicator onto an open panel. 

The BA494G panel mounting kit is manufactured
from the same carbon loaded GRP material as the
indicator  enclosure.    It  provides  an  IP66  seal
between  the  instrument  panel  and  the  indicator
and is therefore suitable for mounting a BA304NG
or  a  BA324NG  in  a  sealed  panel  enclosure.
However,  although  the  BA494G  has  ATEX  and
IECEx  intrinsic  safety  certification,  

the  BA494G

does  not  have  formal  Ex nA  and  Ex tc
certification

.       

Detailed  assembly  instructions  are  supplied  with
each panel mounting kit.

9.6

Back-box terminal assembly

If it is necessary to terminate the field wiring prior
to the installation of the indicator display, a back-
box  terminal  assembly  is  available  as  a  factory
fitted option.   This accessory includes terminals for
the  field  wiring  and  diodes  which  maintain  the
continuity of the 4/20mA loop when the indicator
display is unplugged.

When the indicator display is unplugged from the
back-box,  the  voltage  drop  introduced  into  the
4/20mA loop by the instrument increases to 5V.  If
an  optional  backlight  is  fitted  and  connected  for
loop powering, the voltage drop increases to 11.5V
when  the  indicator  display  is  unplugged.    This
voltage drop can be reduced to 7.5V by connecting
a 7.5V Zener diode with a minimum rating of 1.3W
at 25ºC (BZX85 or 1N5343) between terminals 3
(diode cathode) and 12.(diode anode).

The  optional  terminal  assembly  also  includes
additional terminals which may be used for linking
cable screens and two terminals connected to the
carbon loaded GRP enclosure.  If the enclosure is
not  fixed  to  an  earthed  structure,  one  of  these
terminals or the earth terminal on the bonding plate
should  be  connected  to  the  plant's  potential
equalising conductor.

Fig 19 Optional back-box terminal assembly

Summary of Contents for BA304NG

Page 1: ...Issue 4 1st November 2017 BA304NG BA324NG Ex nA Ex tc loop powered field mounting indicators Issue 4...

Page 2: ...tor 7 3 Under and over range 7 4 Lineariser default configuration 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine maintenance 8 5 G...

Page 3: ...Notified Body Intertek Testing and Certification Ltd which has been used to confirm compliance with the European ATEX Directive 2014 34 EU For international applications both models have IECEx certifi...

Page 4: ...and dust certification This section of the instruction manual describes ATEX gas certification ATEX dust certification is described in Appendix 1 and IECEx approvals are described in Appendix 2 3 1 A...

Page 5: ...to display the measured variable or control signal in engineering units The indicators are transparent to HART signals There are four design requirements 1 The current flowing in the 4 20mA loop must...

Page 6: ...on the rear of the indicator assembly as shown in Fig 5 If the field wiring is to be terminated prior to the installation of the indicator assembly a back box terminal assembly which includes a 4 20m...

Page 7: ...ors are supplied with a printed scale card showing the requested units of measurement and tag information If this information is not supplied when the indicator is ordered a blank scale card will be f...

Page 8: ...r this prompt allowing each digit of the code to be entered using the and push buttons and the button to move control to the next digit When the correct four digit code has been entered pressing will...

Page 9: ...djusted without the need for an accurate input current or disconnection from the 4 20mA loop See section 6 6 bAr Bargraph format and calibration Only the BA324NG has a bargraph The bargraph may be con...

Page 10: ...10...

Page 11: ...not required it should be positioned beyond the most or least significant digit When positioned as required press the button to enter the selection and return to the configuration menu 6 5 Calibration...

Page 12: ...cator s digital display at which the bargraph starts is defined by the bArLo sub function which is selected by pressing the button followed by the button which will reveal the current indicator displa...

Page 13: ...ions shown in sections 6 0 and 7 3 To reset the indicator or lineariser select r5Et from the configuration menu and press the indicator will display one of the reset options ConF or LtAb ConF Resets t...

Page 14: ...ows direct calibration of the lineariser with an external current source and is the preferred method when traceability is required If the exact system non linearity is unknown this method also allows...

Page 15: ...15...

Page 16: ...ng break point 7 1 1 Example Adding break points to a new indicator When adding break points to a new indicator or to a lineariser following resetting to the factory defaults using the LtAb function d...

Page 17: ...n by pressing the button The corresponding indicator display at each of the break points can now be defined using the di5P sub function Using the and buttons select the di5P sub function and press whi...

Page 18: ...o risk of a flammable atmospjher being present If an indicator fails after it has been functioning correctly follow the procedure shown in section 8 1 If this does not reveal the cause of the fault it...

Page 19: ...haracters 5mm high 9 2 Display backlight The BA304NG and BA324NG loop powered indicators can be supplied with a factory fitted backlight that may be loop or separately powered When loop powered the ba...

Page 20: ...s an emergency shut down system Both models can be supplied with factory fitted dual solid state single pole alarm outputs Each alarm output may be independently conditioned as a high or low alarm wit...

Page 21: ...lication in which a BA304NG or BA324NG indicator is displaying the output from a 2 wire transmitter in Zone 2 Alarm 1 is switching a solenoid valve in Zone 2 and alarm 2 is switching a sounder located...

Page 22: ...tpoint The alarm is activated when the indicator display equals the setpoint See section 9 3 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 3 6 no nC Normally open or n...

Page 23: ...23...

Page 24: ...e for fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and pr...

Page 25: ...t having access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This dir...

Page 26: ...plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 18 Fig 18 Displayed value and setpoints on bargraph T...

Page 27: ...supplied with each panel mounting kit 9 6 Back box terminal assembly If it is necessary to terminate the field wiring prior to the installation of the indicator display a back box terminal assembly is...

Page 28: ...o be used for Zone 22 combustible dust applications The indicator should be located where the minimum amount of dust will accumulate on the enclosure and the installation should be as specified in thi...

Page 29: ...USA and Canada A3 0 cETL Mark For installations in the USA and Canada the BA304NG and BA324NG indicators have ETL and cETL Ex nA and Ex tc approval Control Number 4008610 Copies of the Authorisation...

Reviews: