background image

20

9.2.2

Separately powering the backlight

The optional backlight may also be powered from a
separate  safe  area  power  supply  as  shown  in
Fig 12.

Fig 12  Backlight separately powered

The separately powered backlight is a current sink
which  will  draw  a  constant  34.7mA  when  the
supply voltage is equal to or greater than 11V.   At
lower supply voltages the backlight will continue to
function but with reduced brilliance.

The  ATEX  certificate  therefore  only specifies  the
maximum safety input voltage Ui for terminals 12
and 14.

Ui

=

30V

To  strictly  comply  with  the  requirements  of
EN  60079:14

  Electrical  Installation  in  Hazardous

Areas

, each of the wires entering the hazardous

area  should  be  individually  fused  and  contain  a
means  of  isolation.    However,  in  practice
instrumentation  energised  by  a  current  limited
power  supply  that  can  be  switched  off  is  often
considered adequate.

9.3

Alarms

CAUTION

These alarms outputs should not be used
for critical safety applications such as an
emergency shut down system.

Both  models  can  be  supplied  with  factory  fitted
dual solid state, single pole alarm outputs.   Each
alarm output may be independently conditioned as
a  high  or  low  alarm  with  a  normally  open  or
normally closed output in the non-alarm condition.  

When the 4/20mA current powering the indicator is
removed both alarm outputs will open irrespective
of configuration.  The open circuit condition should
therefore be chosen as the alarm condition when
designing an alarm system.    Fig 13 illustrates the
conditions available and shows which are fail safe. 

When an  alarm  occurs  an  alarm  annunciator  on
the indicator front panel is activated and if required
the  numerical  display  can  alternate  between  the
measured  value  and  the  alarm  channel
identification 

ALr1

 or 

ALr2

.

CAUTION

The alarms are activated by the indicator’s
numerical  display.    Use  of  the  Tare
Function  

tArE

  will  change  the  numerical

display,  the  alarms  will  continue  to
function  at  the  original  displayed  value,
but this will correspond to a different input
current.

Fig 13  Alarm outputs

Configurable  functions  for  each  alarm  include
adjustable  setpoint,  hysteresis,  alarm  delay  and
alarm accept.

Summary of Contents for BA304NG

Page 1: ...Issue 4 1st November 2017 BA304NG BA324NG Ex nA Ex tc loop powered field mounting indicators Issue 4...

Page 2: ...tor 7 3 Under and over range 7 4 Lineariser default configuration 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine maintenance 8 5 G...

Page 3: ...Notified Body Intertek Testing and Certification Ltd which has been used to confirm compliance with the European ATEX Directive 2014 34 EU For international applications both models have IECEx certifi...

Page 4: ...and dust certification This section of the instruction manual describes ATEX gas certification ATEX dust certification is described in Appendix 1 and IECEx approvals are described in Appendix 2 3 1 A...

Page 5: ...to display the measured variable or control signal in engineering units The indicators are transparent to HART signals There are four design requirements 1 The current flowing in the 4 20mA loop must...

Page 6: ...on the rear of the indicator assembly as shown in Fig 5 If the field wiring is to be terminated prior to the installation of the indicator assembly a back box terminal assembly which includes a 4 20m...

Page 7: ...ors are supplied with a printed scale card showing the requested units of measurement and tag information If this information is not supplied when the indicator is ordered a blank scale card will be f...

Page 8: ...r this prompt allowing each digit of the code to be entered using the and push buttons and the button to move control to the next digit When the correct four digit code has been entered pressing will...

Page 9: ...djusted without the need for an accurate input current or disconnection from the 4 20mA loop See section 6 6 bAr Bargraph format and calibration Only the BA324NG has a bargraph The bargraph may be con...

Page 10: ...10...

Page 11: ...not required it should be positioned beyond the most or least significant digit When positioned as required press the button to enter the selection and return to the configuration menu 6 5 Calibration...

Page 12: ...cator s digital display at which the bargraph starts is defined by the bArLo sub function which is selected by pressing the button followed by the button which will reveal the current indicator displa...

Page 13: ...ions shown in sections 6 0 and 7 3 To reset the indicator or lineariser select r5Et from the configuration menu and press the indicator will display one of the reset options ConF or LtAb ConF Resets t...

Page 14: ...ows direct calibration of the lineariser with an external current source and is the preferred method when traceability is required If the exact system non linearity is unknown this method also allows...

Page 15: ...15...

Page 16: ...ng break point 7 1 1 Example Adding break points to a new indicator When adding break points to a new indicator or to a lineariser following resetting to the factory defaults using the LtAb function d...

Page 17: ...n by pressing the button The corresponding indicator display at each of the break points can now be defined using the di5P sub function Using the and buttons select the di5P sub function and press whi...

Page 18: ...o risk of a flammable atmospjher being present If an indicator fails after it has been functioning correctly follow the procedure shown in section 8 1 If this does not reveal the cause of the fault it...

Page 19: ...haracters 5mm high 9 2 Display backlight The BA304NG and BA324NG loop powered indicators can be supplied with a factory fitted backlight that may be loop or separately powered When loop powered the ba...

Page 20: ...s an emergency shut down system Both models can be supplied with factory fitted dual solid state single pole alarm outputs Each alarm output may be independently conditioned as a high or low alarm wit...

Page 21: ...lication in which a BA304NG or BA324NG indicator is displaying the output from a 2 wire transmitter in Zone 2 Alarm 1 is switching a solenoid valve in Zone 2 and alarm 2 is switching a sounder located...

Page 22: ...tpoint The alarm is activated when the indicator display equals the setpoint See section 9 3 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 3 6 no nC Normally open or n...

Page 23: ...23...

Page 24: ...e for fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and pr...

Page 25: ...t having access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This dir...

Page 26: ...plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 18 Fig 18 Displayed value and setpoints on bargraph T...

Page 27: ...supplied with each panel mounting kit 9 6 Back box terminal assembly If it is necessary to terminate the field wiring prior to the installation of the indicator display a back box terminal assembly is...

Page 28: ...o be used for Zone 22 combustible dust applications The indicator should be located where the minimum amount of dust will accumulate on the enclosure and the installation should be as specified in thi...

Page 29: ...USA and Canada A3 0 cETL Mark For installations in the USA and Canada the BA304NG and BA324NG indicators have ETL and cETL Ex nA and Ex tc approval Control Number 4008610 Copies of the Authorisation...

Reviews: