F--
Fan control loop 1
F8
Fan speed standard operation, Set1
Variable for the fan speed during normal standard operation and active Set1.
F9
Fan speed during defrosting, Set1
Variable for the fan speed during defrosting and active Set1.
F10
Fan speed standard operation, Set2
Variable for the fan speed during standard operation and active Set2.
F11
Fan speed during defrosting, Set2
Variable for the fan speed during defrosting and active Set1.
F12
Start boost time (in seconds)
If necessary, the fan can be switched on at max. speed for the time period set here, so that it starts in a stable manner. This
parameter only takes effect if the fan is switched on from standstill.
F13
Minimum speed
Here, the lowest value of voltage at which a connected fan still runs is set.
F15
Evaporator fan: Fan mode standard operation
This parameter specifies how the fan is switched on in standard operation. If the controller is in a defrosting phase, the fan
is controlled via parameter
F16
. In continuous operation [F15 = 1], the fan runs when the controller is switched on. In
continuous operation with drip interruption setting [F15 = 2], the fan behaves as in continuous operation but is switched off
for the duration of
F19
when defrosting has ended. After the drip-off time in
F19
has elapsed, the fan is switched on again.
If the compressor is switched on before the time has elapsed, the fan is immediately restarted (after the delay in
F17
). In
the Compressor On setting [F15 = 3], the fan is switched on and off with the compressor. To prevent compressors and fans
from overloading the power supply by starting together, a delay can be set using
F17
.