F66
Condenser fan: P-controller proportional range
For setting the proportional range required for
[F65 = 4
] in which the fan is to be placed.
F67
Condenser fan: Minimum speed
The lowest value of voltage at which a connected fan still runs is set.
F68
Condenser fan: Start boost
This specifies the time with which a stationary fan is switched on with max. voltage so it can start up in a stable manner.
F99
Password for parameter level
F--
This parameter can be used to set the password for parameter level
F--
.
H--Temperature probes and sensors
H1
Mains frequency
This parameter is used to select the mains frequency.
H11
,
H21
,
H31
,
H41
Actual value of sensors F1..F4
The temperature value displayed here is used for control purposes. It is calculated from: Actual control value = (actual
measured value * weight factor ) + actual value correction. The actual value correction and weighting factor must be specified
in the following parameters. In special applications (refrigerated display cabinets or similar), this corrects any actual value
deviation caused by unfavourable positioning of the sensor.
H51
Weighted average of sensors F1 and F2
This calculated average value of sensors F1 and F2 can be useful for the control loop or the display. It is calculated as
follows:
H51
= (
H53
x
H11
+ (100
–
H53
) x
H21
) / 100
H12
,
H22
,
H32
,
H42
Sensor calibration F1...F4 actual value correction
This parameter can be used to correct actual value deviations caused, for example, by sensor tolerances, extremely long
sensor cables or by structural protective circuits (e.g. Ex barriers). The value set here is added to the measured value.
H13
,
H23
,
H33
,
H43
Weighting factor F1…F4
This parameter can be used to correct actual value deviations due to unfavourable positioning of the sensor. The controller
measured value is multiplied by the value set here.
H14
,
H24
,
H34
,
H44
Sensor selection F1…F4
This parameter is used to set the sensor type. Depending on the hardware, not all sensor types can be supported. For the
NTC sensor, a parallel resistor must also be connected.
H15
,
H25
,
H35
,
H45
Software filter F1…F4
This parameter is used to determine the number of measured values from which an average value is calculated. An average
value is formed from the last measured values, whereby the oldest measured value is deleted (so-called "moving average
filter").
H16
,
H26
,
H36
,
H46
F1…F4: Display at 0/4 mA
If
H14
/
H24
/
H34
/
H34
= 7 or 8 (0...20 mA or 4...20 mA linear sensor) is selected for the sensor selection, this parameter can
be used to determine which value is to be displayed at a current of 0 or 4 mA. The display value for 20 mA is specified in
the next parameter. The actual measured value is calculated as linear interpolation between these two values.
H17
,
H27
,
H37
,
H47
F1…F4: Display at 20 mA
If
H14
/
H24
/
H34
/
H34
= 7 or 8 (0...20 mA or 4...20 mA linear sensor) is selected for the sensor selection, this parameter can
be used to determine the value that is to be displayed at a current of 20 mA. The display value for 0 or 4 mA is specified in
the previous parameter. The actual measured value is calculated as linear interpolation between these two values.
H53
Weighting of sensor F1 for display
H51
(weighted average value of sensors F1 and F2)
This calculated average value of sensors F1 and F2 can be useful for the control loop or the display. It is calculated as
follows:
H51
= (
H53
x
H11
+ (100
–
H53
) x
H21
) / 100
H99
Password for parameter level
H--
This parameter can be used to set the password for parameter level
.