L-- Networking and display
Parameter
Functional description
Setting range
Factory values
Customer
values
Arctis/
Duplex
Vulcano Cold Rack/
Showcases
L0
ST bus, own address, identical to
the
Adr
setting.
1...250
80
80
80
L1
8
1...255
2
2
2
L2
Temperature scale.
0: Celsius
1: Fahrenheit
0
0
0
L3
Display mode for actual value.
0: Integer
1: Resolution 0.5 K
2: Resolution 0.1 K
2
2
2
L4
Actual value, parameter address. 0...255
0
0
0
L4b
Actual value 2, parameter
address.
0...255
2
2
2
L5
Request cycle for measured
value.
1...99.9 s
1.0
s
1.0
s
1.0 s
L6
Own software version.
L7
Display during standby.
0: OFF
1: OFF
2: Right decimal point
3: Right decimal point flashing
0
0
0
L8
Key lock function.
0: No lock
1: Setpoint displayed, cannot be
adjusted
2: Setpoint not displayed
3:
PA
and
PAE
levels read only
4:
PA
level read only,
PAE
level
not displayed
5. Function keys deactivated
0
0
0
L9
Read/display status.
0: Read and display status
1: No status, display shows measured
value
0
0
0
L13
Setpoint offset or Setpoint 1.
0: Inactive
1: Setpoint
c1
1
1
1
L15
Behaviour of function keys with
standby/controller off.
0: Function keys are deactivated
1: Function keys active
0
0
0
L16
Setpoint offset or Setpoint 2 (key
assignment with
b1 …b10
setting 18…21).
0: Inactive
1: Setpoint
(c1)
2: Setpoint Set2
(c3)
3: Setpoint of 2nd control loop
(Y1)
4: Humidity setpoint
(c31)
5: Humidity setpoint Set2
(c33)
6: Triac setpoint
(U10)
3
3
3
L30
Display mode for actual value
(display 2 if present).
0: Integer
1: Resolution 0.5 K
2: Resolution 0.1 K
2
2
2
L31
Actual value, parameter address
(display 2 if present).
0...255
18
18
18
PA
Level selection password for
internal level (satellite display).
- 99...999
- 19
- 19
- 19
PAE
Level selection password for
external access (levels in the
connected controller).
- 99...999
- 38
- 38
- 38
L99
Password for access to
parameter list
L--
- 99...999
0
0
0
* Parameters
L0, L1, PA
and
PAE
can only be viewed and set via the ST bus.