Parameter
Functional description
Setting range
Factory values
Customer
values
Arctis/
Duplex
Vulcano Cold
Rack/
Showcas
es
A16
Recurring buzzer after
acknowledgement.
1 ... 120 min
30
30
30
A17
Reset MIN/MAX memory.
0: -
1: Reset MAX memory
2: Reset MIN memory
3: Reset MAX and MIN memory
0
0
0
A18
Display of the current MAX memory. Measured value, not adjustable
A19
Display of the current MIN memory.
Measured value, not adjustable
A20
High-pressure switch function
Triggers until permanent alarm.
0: No permanent alarm
1..10: Triggers every 15 min
0
0
0
A25
Low-pressure switch function. Delay
until permanent alarm.
0: No permanent alarm
1...300 s
0
0
0
A99
Password for parameter level
A--
- 99 ... 999
0
0
0
b--
Keys and switch inputs (password-protected)
Parameter
Functional description
Setting range
Factory values
Customer
values
Arctis/
Duplex
Vulcano Cold
Rack/
Showc
ases
b11
Function of external
switching input E1.
0: No function
1: Controller on/standby
2: High-pressure alarm (see
A20
3: Low-pressure alarm (see
A25
4: Door contact (light on, fan off, see also
A13
5: Relay function A (light 1), not active during standby
6: Relay function A (light 1), independent of standby
7: Relay function B (light 2), not active during standby
8: Relay function B (light 2), independent of standby
9: Relay function C (window heating), not active
during standby
10: Relay function C (window heating), independent of
standby
11: Relay function D (door frame heating), not active
during standby
12: Relay function D (door frame heating), independent
of standby
13: Relay function E (knife wiper), not active during
standby
14: Relay function E (knife wiper), independent of
standby
15: Relay function F, not active during standby
16: Relay function F, independent Standby
17: Set1/Set2 changeover
18: Day/Night changeover
19: "Superfrost" on/off (see also
c21 …. c23
)
20: Evaporator fan permanently on
21: Defrost request, circuit 1
22: Defrost request, circuit 2
23: Control loop 1 on/off
24: Control loop 2 on/off
25: As 17, remember status after power failure
26: As 6, remember status after power failure
27: As 8, remember status after power failure
28: External alarm
0
0
0