Commissioning
5
Commissioning
5.1
Charging time
The charging time of the UPS module depends on actual the discharge and can not be measured exactly. It
is possible to estimate the "maximal charging time". This time describes the charging behavior of completely
discharged storage cells. The test units were discharged over night. Then the time to system start was
measured. The following table shows the results of the measurements.
Charging time
Model
Charging time
CX1100-0900
42 s
CX1100-0910
46 s
CX1100-0920
116 s
CX1100-0930
65 s
Note
The given times are average values. In operation the time for discharging must be added to
the time. In mode "No Abort" e.g. the storage cells will be discharged before the charging
starts.
CX1100-09xx
19
Version: 1.4