Commissioning
"CX1190 UPS" tab:
Enable Automatic Shut Down:
If this switch is selected, then TwinCAT is stopped after an adjustable retention time, and "Windows XPe" is
shut down. Device 1 (here the CX1100) is switched off after the retention time has elapsed. Even when the
power fails for very short periods (<<10s) the system shuts down and the CX10x0 is switched off.
No Abort:
If the power voltage returns after TwinCAT has stopped, but while "Windows XPe2" is still shutting down, the
CX10x0 will still reboot.
The problem of staying stuck in OFF, as above (option 1) does not occur. As soon as the UPS is fully
charged again, the CX switches on once more.
Problem:
The CX10x0 boots in every case, even when power failures are extremely short
Using the System Manager to set the retention time
The retention time of the UPS is set through the rotary switch on the front panel of the UPS. Details on this
can be consulted in the
of the switch. It is possible to ignore this setting, and to
set the retention time of the UPS through the System Manager. This is done by selecting the "Override DIP
Switch" dialog box. The "DIP Switch" check box is activated here. A value from 0 to 9 can be chosen. This
value corresponds to the setting of the rotary switch. The position of the rotary switch no longer has any
effect.
CX1100-09xx
29
Version: 1.4