INSTALLER GUIDE
Page 21
4.
Fit the two “U” section seals to the bottom edges of the
convection box side flanges (See figure 13).
5.
It is important that the grommet supplied in the
loose parts pack is fitted to the hole in the rear of the
convection box.
6.
For concealed connection only:
Pierce the grommet to allow the pipe to pass through it.
The grommet should envelop the pipe. If the hole is larger
than the pipe, seal it with tape.
Do not pierce the
grommet unless the supply pipe is to pass through it
.
7.
The appliance is supplied with two fireback spacers
that must be fitted in all installations.
These should
extend backwards to ensure sufficient clearance from the
back of the fireplace. Position the fireback spacer as
shown in figure 14. Secure the fireback spacers
using the four tapping screws supplied with the fire.
8.
This appliance is supplied with a flue restrictor for
use where the flue draught is excessive. Generally
we recommend the restrictor is NOT fitted where a
precast flue, metal flue box or a flue liner is used,
however, certain flues may work sufficiently to
warrant its use. There may however, be
circumstances where fitting the restrictor causes the
fire to fail the spillage test. In such cases the
restrictor will have to be removed. After removal
conduct the spillage check again.
The restrictor is packed loose with the appliance and
is fixed with three screws (See figure 15).
©
Baxi Heating U.K. Limited 2010.
Figure 15. Flue restrictor
Figure 14. Fireback
spacers.
Figure 13. ‘U’ Seals