PD-TaD 62
Completing a measurement at a later point in time
822-187-3
97 / 114
This chapter discusses how to continue a parallel PD and dissipation factor measurement
and a Full MWT measurement.
If you have saved the log following cancellation of the dissipation factor measurement or
MWT measurement and the PD test, you can complete this measurement at a later point in
time.
1. Depending on the diagnostics type, select the following menu item and press the rotary
knob to confirm:
Parallel PD and dissipation factor measurement:
Main menu
>
VLF Diagnostics
–
tan
>
Logs
>
tan
Measurement
Full MWT:
Main menu
>
VLF Diagnostics
– tan
>
Logs
>
MWT with tan
If the measurement is not complete, this is indicated by a cross.
2. Select the relevant log and press the rotary knob to confirm.
3. In the context menu, select the menu item
Continue measurement
and press the rotary
knob to confirm.
The measurement mode window opens.
Important:
To be able to compare the results, set the same measurement conditions.
Further information:
Chapter
Performing parallel PD and dissipation factor measurements
(on page 66)
Chapter
Performing a Full MWT measurement
(on page 76)
16
C
OMPLETING A MEASUREM ENT AT A LATER POINT IN
TIME