PD-TaD 62
Connecting the system
822-187-3
53 / 114
No.
Cable
Step
8
HV connection cable of
the VLF HV generator
Connect the screen of the HV connection cable to the
Screen (HV Cable)
port.
9
See above
Connect the HV connection cable to the HF filter at the
HV IN
port.
Further information: Chapter
Connecting the HF filter to the PD-TaD 62
(on
10
Short-circuit cable of
PD-TaD 62
On the PD-TaD 62, remove the short-circuit cable from ports
HV IN
and
HV OUT
.
At the far end of the test object:
11
–
Clean the cable termination of the phase to be tested carefully.
12
–
Attach the anti-corona hoods of the anti-corona protection device to the
cable termination of the phase to be tested.
13
Protective ring
(conductive hook and
loop fastener tape)
Attach a protective ring to the cable termination of the phase to be tested
–
directly over the screen.
Important:
Ensure that the protective ring does not come into contact with
the screen.
14
VSE cables with 2
connection clips
(yellow)
Use the VSE cable to short-circuit the protective ring to a de-energised
phase on which no measurement is to be taken.
The de-energised phase is used as a return circuit for leakage currents from
the far end.
At the near end of the test object:
15
–
Clean the cable termination of the phase to be tested carefully.
16
–
Attach the anti-corona hoods of the anti-corona protection device to the
cable termination of the phase to be tested.
17
Protective ring
(conductive hook and
loop fastener tape)
Attach a protective ring to the cable termination of the phase to be tested
–
directly over the screen.
Important:
Ensure that the protective ring does not come into contact with
the screen.