PD-TaD 62
Parallel partial discharge and dissipation factor measurement
822-187-3
65 / 114
1. In the main menu, select the menu item
VLF Diagnostics
– tan
and press the rotary
knob to confirm.
2. In the
VLF Diagnostics
– tan
menu, select the menu item
tan
Measurement
and
press the rotary knob to confirm.
3. Select the
IEEE 400.2
menu item and press the rotary knob to confirm.
The
IEEE 400.2
window opens.
4. Set the following parameters:
Voltage U (phase
– phase)
Setting range: In accordance with the specifications of the draft IEEEIEEE 400.2 (the
max. test voltage according to the respective VLF HV generator)
Number of measurements per voltage step (1 - 20)
Number of phases (1 - 3)
Test type
The following test types are available: Installation, acceptance inspection
(commissioning) and maintenance.
The max. voltage is automatically determined and displayed after voltage U (phase
–
phase) has been entered.
5. Select the
Next
menu item and press the rotary knob to confirm.
The dialog for selecting the evaluation opens. The cursor is in the input field for the
evaluation.
6. Press the rotary knob in order to select an evaluation.
7. In the context menu, select whether you wish to use evaluation criteria for America or for
other countries (World) according to IEEE 400.2, and press the rotary knob to confirm.