on. The VLF HV generator no longer delivers dangerous voltage. A safety message appears
which prompts you to discharge, earth and short-circuit the test object.
On completion of a measurement stage you have the following options:
Carry out the next measurement stage (ramp-up or MWT) on the same phase
Proceed as follows:
1. In the lower menu bar, select the menu item
Start
.
2. In the context menu, select the next measurement stage on the same phase.
3. Repeat the measurement.
Further information: Chapter
Performing a Full MWT measurement
(on page 76)
Starting a measurement on another phase
DANGER
Dangerous voltage at test object and other live plant parts.
Danger to life or risk of injury due to electric shock.
Before touching the test object, discharge, earth and short it: at the
connection point and at the far end.
You may touch the plant parts that were under voltage only if they
are visibly earthed and short-circuited.
1. Discharge and earth the
HV IN
and
HV OUT
ports of the HV coupling unit with the
discharge rod of the VLF HV generator (standard delivery of VLF HV generator).
2. Disconnect the connected phase.
3. Connect the required phase.
Further information: Chapter
Connecting the system for parallel PD and dissipation factor
measurement or Full MWT
(on page 43)
4. In the lower menu bar of the VLF HV generator menu, select the menu item
Start
and
perform the measurement.
Further information: Chapter
Performing a Full MWT measurement
(on page 76)
Note:
You have the option of completing the measurement at a later point in time. Further
information: Chapter
Completing a measurement at a later point in time
(on page 97)