PD-TaD 62
Parallel partial discharge and dissipation factor measurement
822-187-3
67 / 114
This means that:
the PD-TaD 62 has been recognised by the VLF HV generator,
the dissipation factor measurement is measured using the external resistance of the
PD-TaD 62.
4. If
R-TD external
is not displayed in the measurement mode window:
a. Check the ports on the VLF HV generator (port
PD Detector
) and the PD-TaD 62
(port
VLF Generator
).
b. If the ports are OK, contact your nearest BAUR representative
(http://www.baur.eu/baur-worldwide).
Note:
If the PD-TaD 62 is connected, but not recognised by the VLF HV generator, the
measurement results will be highly distorted.
5. In the bottom menu bar, select
Start
and press the rotary knob to confirm.
If only one phase is specified in the program for the dissipation factor measurement
template used, a prompt for high voltage release appears. This will take you to the next
step.
Measurement on several phases
If more than one phase has been specified in the program, a context menu for phase
selection opens. The phases on which the measurement has already been carried out
are indicated by means of a tick. If the measurement on a phase was cancelled, this is
indicated by a cross.
a. Turn the rotary knob to select a phase, and then press the rotary knob to confirm.
You have the option to repeat the measurement on a phase.
The prompt for connecting the selected phase appears on the display.
b. If the selected phase has not yet been connected, it must be connected.
Further information: Chapter
Connecting the system for parallel PD and dissipation
factor measurement or Full MWT
(on page 43)
c. Select the menu item
Next
.
The prompt for high voltage release appears on the display.
6. Hold down the
key for at least one second.
The VLF HV generator switches to the
Ready for operation
operating state. The red
indicator light flashes for approx. 6 seconds. The prompt for switching on the high
voltage appears on the display:
Press button <High voltage on>
.
If you wish to cancel the high voltage release and return to the measurement mode
window, press the rotary knob.
7. Press the
key whilst the red indicator light is flashing.
The VLF HV generator switches to the
In operation
operating state. The red indicator
light comes on.