Connecting the system
PD-TaD 62
40 / 114
822-187-3
No.
Cable
Step
On the laptop:
4
USB cable
For the remote control of the VLF HV generator: Use a USB cable to
connect the laptop to the VLF HV generator.
5
Ethernet cable
Use the supplied Ethernet cable to connect the laptop to the Power Box
(
Laptop
port).
–
–
If you do not want to run the laptop off its battery, connect the laptop to the
Power Box to establish a power supply. To do so, use the connection cable
with the C14G plug.
At the PD-TaD 62:
6
PoE cable
Connect the PoE cable:
to the Power Box (
PD Detector
port) and
to PD-TaD 62 (
Power Box
port)
This is used for power supply and data transmission at the same time.
7
–
Connect the HF filter to the
HV IN
port.
Further information: Chapter
Connecting the HF filter to the PD-TaD 62
(on
8
HV connection cable of
the VLF HV generator
Connect the HV connection cable to the HF filter at the
HV IN
port.
Further information: Chapter
Connecting the HF filter to the PD-TaD 62
(on
9
Short-circuit cable of
PD-TaD 62
On the PD-TaD 62, remove the short-circuit cable from ports
HV IN
and
HV OUT
.
At the far end of the test object:
10
–
Clean the cable termination of the phase to be tested carefully.
11
–
Attach the anti-corona hoods of the anti-corona protection device to the
cable termination of the phase to be tested.
At the near end of the test object:
12
–
Clean the cable termination of the phase to be tested carefully.
13
–
Attach the anti-corona hoods of the anti-corona protection device to the
cable termination of the phase to be tested.
14
HV connection cable of
PD-TaD 62
Connect the PD-TaD 62 (
HV OUT
port) to the phase to be tested.
To do this, select the shorter of the two supplied HV connection cables.
Place the HV connection cable as far away as possible from the adjacent
live and earthed parts.
At the near and far end of the test object:
15
–
Remove the earthing and short-circuit connection from the phase to be
tested.
Make sure that the phases not being tested are earthed and short-circuited.