Configure PDOs
The PDOs can be configured according to the following table:
1906h
Sub2
Sub5
2800h
Brief Description
FFh
3ms
0
Cyclical transmission every 3 ms
FFh
5ms
2
PDO is sent double every 5 ms if a change exists.
FFh
0ms
0
Send PDO deactivated
FFh
0ms
2
Send PDO deactivated
3
xxx
0
Send during every third Sync telegram
3
xxx
2Bh
Every third Sync telegram, but total of only 43 times (=2Bh).
Specify Heartbeat Time
To monitor the communication capability, the time of the heartbeat must be defined in Object 1017h
"Producer Heartbeat Time". As soon as the value has been confirmed, the service begins to transmit. For
example, the encoder is to send a heartbeat every 100 ms (100 = 64h):
COB-ID
DLC Command
Object L
Object H
Subinde
x
Data
0
Data 1
600h+Node-ID
8
2Bh
17h 10h 0h 64h
0h
Confirmation:
COB-ID
DLC Command
Object L
Object H
Subinde
x
Data
0
Data 1
580h+Node-ID
8
60h
17h 10h 0h 0
0
COB-ID
Data/ Remote Byte 0
701h d
7Fh
The Heartbeat messages consist of the COB-ID and a byte. The NMT state is transmitted in this byte.
0:
BootUp
event
4:
Stopped
5:
Operational
127:
Pre-Operational
This means the encoder is in the Pre-Operational mode (7Fh = 127).