Fault
Cause
Remedy
Reset button cannot be
acknowledged
1. Emergency stop switch is pressed
2. PT100 Sensor from HELIX pump
triggered
3. Phase line from power connection
reversed
4. Level switch triggered ( Option)
5. Break through protection triggered
(option)
1. Check emergency stop switches
2. Check PT 100 Sensor possibly
change setting ( see operation
manual PT 100 Sensor and JUMO
Device)
3. Change phase line of power con-
nection ( rotation control device
does not light up, see chapter 7.3)
4. If installed: check connection of
level switch and correct function,
check connection cable
5. If installed: check connection of
break through protection and con-
nection cable of break through
protection
System is shuts down in au-
tomatic mode
1. Pressure in the inlet pipe too high
(Status LED on pressure switch
lights up red)
2. Break through protection triggered
3. Level switch triggered
4. PT 100 Sensor from Helix pump
triggered
1. not the correct screen for this ap-
plication installed (use screens
with larger or smaller slots)
2. Check break through protection
switch, possibly build up a new
starter cake see chapter 7.8. in
case of repeating check, wash or
change screens, check cable
3. Check level switch, slurry pit
empty, Level switch cable faulty
4. Check PT 100 Sensor, Helix pump
is running dry, check suction line
and slurry level in pit
Fault of an respective
component
1. See operation manual of respec-
tive system component
Problems that cannot
be corrected
A problem as described
above cannot be cor-
rected despite optimal
configuration according to
the instructions given
above.
Document any errors, faults and
the taken measures to correct the
problem.
Contact your dealer or BAUER
company for further information.
Please always have the serial
number ready.