General
Description

The Series TY-B, 5.6 K-factor, Horizon-
tal and Vertical Sidewall Sprinklers de-
scribed in this data sheet are standard
response - standard coverage, deco-
rative 5 mm glass bulb type spray
sprinklers designed for use in light and
ordinary hazard, commercial occupan-
cies such as banks, hotels, shopping
malls, etc. They are designed for instal-
lation along a wall or the side of a beam
and just beneath a smooth ceiling.
Sidewall sprinklers are commonly
used instead of pendent or upright
sprinklers because of aesthetics or
building  construction  considerations,
where piping across the ceiling is not
desirable.

The recessed version of  the Series
TY-B Horizontal Sidewall Sprinkler is
intended for use in areas with a fin-
ished wall. It uses a two-piece Style 10
Recessed Escutcheon. The Recessed
Escutcheon provides 1/2 inch  (12,7
mm) of recessed adjustment or up to
3/4 inch (19,1 mm) of total adjustment
from the flush sidewall position. The
adjustment provided by the Recessed
Escutcheon reduces the accuracy to
which the fixed pipe nipples to the
sprinklers must be cut.

Corrosion resistant  coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these corrosion resistant coatings
for any given corrosive environment.
The effects of ambient temperature,
concentration of chemicals, and
gas/chemical velocity, should be con-

sidered, as a minimum, along with the
corrosive nature of the chemical to
which the sprinklers will be exposed.

WARNINGS

The Series TY-B Sprinklers described
herein must be  installed and  main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the integrity of these devices.

The owner is responsible for maintain-
ing their fire protection system and de-
vices in  proper operating  condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.

Model/Sprinkler
Identification
Numbers

TY3351 -

Horizontal

TY3451 -

Vertical

Technical
Data

Approvals

UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A for complete approval
information including corrosion resis-
tant status)

Maximum Working Pressure

175 psi (12,1 bar)

Discharge Coefficient

K = 5.6 GPM/psi

1/2

(80,6 LPM/bar

1/2

)

Temperature Ratings

Refer to Table A

Finishes

Sprinkler: Refer to Table A
Recessed Escutcheon: White Coated
or Chrome Plated. (Other colors are
available on request.)

Physical Characteristics

Frame

. . . . . . . . . . . . Bronze

Button

. . . . . . . .

Brass/Copper

Sealing Assembly . . . . . . . . . .

. . . . . . Beryllium Nickel w/Teflon†

Bulb

. . . . . . . . . . . . . . Glass

Compression Screw . . . . . Bronze
HSW Deflector . . . . . . . . Bronze
VSW Deflector . . . . . . . . Copper

Patents

U.S.A. Patent Number 5,810,263 and
UK Patent Number 2,347,624 may be
applicable to the Series TY-B Horizon-
tal Sidewall Sprinkler.

D

uP

on

t

R

eg

is

tere

d

T

rad

ema

rk

Series TY-B — 5.6 K-factor
Horizontal and Vertical Sidewall Sprinklers
Standard Response, Standard Coverage

Technical Services:

Tel: (800) 381-9312 / Fax: (800) 791-5500

Page 1 of 6

TFP161

FEBRUARY, 2002

Customer Service/Sales:

Tel: (215) 362-0700 / (800) 523-6512

Fax: (215) 362-5385

TFP161 (1-6.1)

OBSOLETE

Summary of Contents for CENTRAL TY-B

Page 1: ...perature concentration of chemicals and gas chemical velocity should be con sidered as a minimum along with the corrosive nature of the chemical to which the sprinklers will be exposed WARNINGS The Series TY B Sprinklers described herein must be installed and main tained in compliance with this docu ment as well as with the applicable standards of the National Fire Protec tion Association in addit...

Page 2: ... of deflector to ceiling distance 4 Approved by the Loss Prevention Certification Board LPCB at a 4 to 6 inch 100 to 150 mm deflector to ceiling distance 5 Listed by Underwriters Laboratories Inc UL for use in Light and Ordinary Hazard Occupancies 6 Listed by Underwriters Laboratories Inc for use in Canada C UL for use in Light and Ordinary Hazard Occupancies 7 Approved by Factory Mutual Research ...

Page 3: ...er Wrench or the Crescent wrench as applicable is to be applied to the wrench flats When installing wax coated sprinklers with the adjustable Crescent wrench additional care needs to be exercised to prevent damage to the wax coating on the sprinkler wrench flats or frame arms and consequently exposure of bare metal to the corrosive environ ment The jaws of the wrench should be opened sufficiently ...

Page 4: ...from the proper authorities and all personnel who may be affected by this action must be notified Absence of an escutcheon which is used to cover a clearance hole may delay the time to sprinkler operation in a fire situation Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced Automatic sprinklers must never be shipped or stored where their tempera ture...

Page 5: ...isdiction Mate rials found by Tyco Fire Products to be defective shall be either repaired or replaced at Tyco Fire Products sole option Tyco Fire Products neither as sumes nor authorizes any person to assume for it any other obligation in connection with the sale of products or parts of products Tyco Fire Products shall not be responsible for sprinkler system design errors or inaccurate or incompl...

Page 6: ... color coded Wax Stick for retouching specify tem perature rating temperature rated Se ries TY B Sprinklers P N specify Black for 135 F P N 56 065 1 135 Red for 155 F P N 56 065 1 155 Yellow for 175 F P N 56 065 1 175 Blue for 200 F and 286 F P N 56 065 1 286 NOTES Each wax stick is suitable for retouch ing up to twenty five sprinklers The wax used for 286 F sprinklers is the same as for 200 F spr...

Reviews: