PROFIBUS
111
Operating Instructions HYGROPHIL® H 4230-10 Serie A BA 030520
ControlStatusChar:
Used to control the valve within the unit, especially to switch off the valve
temporarily when errors occur. Overrides the PropValveConfig up to reset.
Control
Status
7
6
5
4
3
2
1
0
ON
FullOpen
FullClose
Free
ON
FullOpen
FullClose
Free
ON:
1 = Controller is switched on and working
0 = Controller off
FullOpen:
1 = Valve completely open (Control) or opened (Status)
0 =
No „FullOpen“
ON time:
Time in µs during which the valve is activated.
OFF time.
Time in µs during which the valve is not activated.
DaAdr $54: PumpControlStatus
Format: Char
7
6
5
4
3
2
1
0
ON
Pump on/off FillMode
Control
NormalMode
Control
SM-Error
Free
FillMode
Status
NormalMo
de
ON:
1 = The pump is switched on and running
0 = Pump not in operation
Pump on/off:
1 = Pump is currently active
0 = Pump is currently not active
FillMode Control:
1 = Pump is switched to fill mode
0 = No fill mode
SMError:
1 = Error in the stepper motor
0 = No error in the stepper motor
FillMode:
1 = Pump is running in the mode for filling the system
0 = No fill mode
NomalMode: 1 = Pump is running at the speed specified under
PumpConfig
0 = No normal operation
DaAdr $55: PumpConfig
Format: Char
Before you can write this variable you must first change to standby mode.
Specification of the pump speed: default 25 -35