PROFIBUS
107
Operating Instructions HYGROPHIL® H 4230-10 Serie A BA 030520
DaAdr $39: OutputChConfig*
Format: Array [1...2] of Record
Output1
Output2
EnableBits:
Char (*Offset = 0*) Char (*Offset = 4*)
FunctionBits:
Char (*Offset = 1*) Char (*Offset = 5*)
SetpointNo:
Char (*Offset = 2*) Char (*Offset = 6*)
ErrorState:
Char (*Offset = 3*) Char (*Offset = 7*)
End;
Before you can write this variable you must first change to standby mode.
EnableBits:
Settings for various checks and error relevance, etc.
7
6
5
4
3
2
1
0
Free
HighAlarm
LowAlarm
Free
Free
Free
Free
Free
0
Default
1
1
0
0
0
0
0
Functions:
$00 = Output disable
$10 = Current output 0...100%: 4-20 mA
$20 = Current output 0...100%: 20-4 mA
$30 = Current output 0...100%: 0-20 mA
$40 = Current output 0...100%: 20-0 mA
Default = $10
SetpointNo:
Index for selecting the output variable 0...15, based on the table in DaAdr
$10 and further with the table in DaAdr $20
e.g. SetpointNo = 2 => SP appears at the analogue output
Default Setpoint[1] = 6(DT), Setpoint[2] = 7 (RH), Setpoint[3] = 8 (VP);
ErrorState:
Behaviour of the analogue outputs when equipment errors occur:
7
6
5
4
3
2
1
0
Free
Free
1
OutStart-1
Free
Free
OutEnd
OutStart
0
Default
0
0
0
0
0
0
0
OutStart:
1 = 0mA at 0...20mA, 4mA at 4...20mA,
20 mA at 20...4mA or 20...0mA
OutEnd:
1 = 20mA at 0...20mA or 4...20mA,
4 mA at 20...4mA, 0mA at 20...0mA
OutStart-1:
1 = 0mA at 0...20mA, 3mA at 4...20mA,
21 mA at 20...4mA or 20...0mA
1:
1 = 21mA at 0...20mA or 4...20mA,
3 mA at 20...4mA, 0mA at 20...0mA