2. View the current mode.
Action
Result
Double-pulse the remote input.
T
T
T
The current mode displays.
3. Program the sensor.
Action
Result
Pulse the remote input 1 to 6 times to select the desired mode.
Pulses
Mode
1
T
Alarm
2
T
T
T
Health
3
T
T
T
T
T
Swtch
4
T
T
T
T
T
T
T
Swtch
5
T
T
T
T
T
T
T
T
T
Wnd
6
T
T
T
T
T
T
T
T
T
T
T
Wnd
The selected mode flashes and the sensor
returns to Run mode.
3.5.8 Switch Point Reference (SPtRef)
The SPtRef menu only displays for a discrete output when it is set to switch mode. This setting cannot be changed with
remote teach.
• Object (default). Object mode automatically optimizes the switching threshold just past the taught distance, farther
away from the sensor's face.
• Background. Background mode automatically optimizes the switching threshold just in front of the taught distance,
closer to the sensor's face.
• Custom. Custom mode allows the user to define the location of the switching threshold relative to a taught distance
using the Offset menu that appears only after selecting Custom Switch Point Reference.
In Object or Background, the distance between the taught surface and the switching threshold varies depending on
measurement stability. Use object mode when teaching an object if a change in state is required when the object is no
longer present. Use background mode when teaching background so that the output state changes when a new object is in
front of the background.
Navigate: MENU > D_OUT > SPtRef
Remote Input: Not available
Default: Object
3.5.9 Switch Point TEACH Offset
Use this menu to set an offset from the taught distance after a switch point TEACH, if SPtRef is set to Custom.
By default, the value is 0 mm. A positive offset value always shifts the threshold towards the sensor.
Navigate: MENU > Dx_OUT > TchMd > Offset
Remote Input: Not available
Default: 0 mm
L-GAGE
®
LTF Time of Flight Laser Distance Sensor with IO-Link
18
www.bannerengineering.com - Tel: + 1 888 373 6767