Mode
Description
Alarm
Alarm Mode: The Discrete Output is Off while a target is detected by the sensor at any distance.
When a loss of signal occurs, the Discrete Output is On.
This mode has no associated thresholds.
Health
Health Mode: The Discrete Output is On while a target is detected by the sensor at any distance.
When a loss of signal occurs, the Discrete Output is Off.
This mode has no associated thresholds.
Switch
Switch Mode: The Discrete Output is On while a target is detected nearer than the switch point threshold.
When a target is detected farther than the switch point threshold or the signal is lost, the Discrete Output is Off.
Switch
Switch Mode: The Discrete Output is Off while a target is detected nearer than the switch point threshold.
When a target is detected farther than the switch point threshold or the signal is lost, the Discrete Output is On.
Wnd
Window Mode: The Discrete Output is On while a target is detected between the SPt1 and SPt2 thresholds.
(Default)
When a target is detected outside the SPt1 and SPt2 thresholds or the signal is lost, the Discrete Output is Off.
Wnd
Window Mode: The Discrete Output is Off while a target is detected between the SPt1 and SPt2 thresholds.
When a target is detected outside the SPt1 and SPt2 thresholds or the signal is lost, the Discrete Output is On.
Remote Input Instructions
1. Access the setup mode.
Action
Result
Double-pulse the remote input.
T
T
T
"REMOTE SETUP" displays.
2. View the current mode.
Action
Result
Double-pulse the remote input.
T
T
T
The current mode displays.
3. Program the sensor.